Ronan Interface System User Manual

Specifications, Interface system

Advertising
background image

Ronan Engineering Company · 8050 Production Drive Florence, KY 41042

(859) 342-8500 · FAX (859) 342-6426

Web: www.ronanmeasure.com · E-Mail: [email protected]

SPECIFICATIONS

Interface System

Environmental

Operating Temperature
Storage Temperature
Humidity
Area Classification

Motor Panel

-30°C to 80°C
-40°C to 80°C
0 – 100%
Barrier Used where intrinsic safety
is required
Class II, Div 2 with Purge
Recommended for corrosion
protection

Control Panel

0 to 50°C
-40°C to 80°C
5 – 95% (non-condensing)
Non Required

Electrical

Supply Voltage

Power required

Drive
Position Sensor
Output

Connections

52 VDC, 3A Max from Control
Panel
12 VDC, .15A from Control Panel

Brushless D.C. motor
Motor Resolver

90 – 250 VAC, 50-60 Hz +/-
10%

120 Watts Continuous
300 A (0-p) 1.0 mSec

Level: 0-20mA/0-10V
Density: 0-20mA/0-10V
3-lug terminal block for AC
power
2-slot terminal blocks for
Level/Density outputs

Cabling (between Motor Panel and Control Panel, tested to 1000 feet)

1-500 feet distance:

501 to 1000 feet distance:

16 Ga, 4 Cond w/.shield (motor pwr)
18 Ga, 6 Cond w/shield (detector)
22 Ga, 12 Cond w/shielded pairs (resolver feedback)
22 Ga, 19 Cond w/shield (panel status)

16 Ga, 4 Cond w/shield (motor pwr)
18 Ga, 6 Cond w/shield (detector)
18 Ga, 12 Cond w/shielded pairs (resolver feedback)
18 Ga, 19 Cond w/shield (panel status)

Interface System