AQU243-4F, AQU243-8F & AQU126-4F Installation Instructions

AQU126-4F, AQU243-4F & AQU243-8F Instructions Doc. # 500-33035 Rev. B

Page 4 of 6

Battery Selection

The table below shows typical standby time in hours for various loads and batteries. The table works for either
AQU243-4F (&-8F) 24v, or AQU126-4F 12v.
Approximate Battery Standby Time Table with a reserve of 3 Amps for 5 minutes for Alarm

Total Output

Amps

4Ah Battery

Standby

7Ah Battery

Standby

12Ah Battery

Standby

24Ah

Standby

40Ah

Standby

.5A

5.5 Hrs

12 Hrs

20 Hrs

40 Hrs

65 Hrs

1A

2.5 Hrs

5 Hrs

9 Hrs

19 Hrs

32 Hrs

1.3A

2 Hrs

4 Hrs

7.2 Hrs

15.5 Hrs

24 Hrs

2A

1 Hrs

2 Hrs

5 Hrs

10 Hrs

15 Hrs

3A

.5 Hrs

1 Hrs

3 Hrs

6 Hrs

9.5 Hrs

4A

.5 Hrs

.8 Hrs

2 Hrs

4 Hrs

8 Hrs

5A

NA

.6 Hrs

1.4 Hrs

3 Hrs

7 Hrs

6A

NA

.4 Hrs

1 Hrs

2 Hrs

4 Hrs

The recharge table below gives approximate recharge times for different loads and battery sizes. The table is based
on batteries depleted to battery cut-off and recharged back to approximately 90% capacity.

Approximate Battery Recharge Times in Hours

Total Output

Amps

4Ah Battery

12v/24v

7Ah Battery

12v/24v

12Ah Bat

12v/24v

24Ah Bat

12v/24v

40Ah Bat

12v/24v

.5A 8Hrs/8Hrs

10Hrs/10Hrs

13Hrs/13Hrs 14Hrs/15Hrs 24Hrs/24Hrs

1A 8Hrs/8Hrs

10Hrs/12Hrs

13Hrs/13Hrs 14Hrs/15Hrs 24Hrs/24Hrs

1.3A 8Hrs/12Hrs

10Hrs/12Hrs

13Hrs/16Hrs 14Hrs/16Hrs 24Hrs/26Hrs

2A 8Hrs/14Hrs

10Hrs/12Hrs

13Hrs/16Hrs 14Hrs/17Hrs 24Hrs/28Hrs

3A 8Hrs/16Hrs

10Hrs/16Hrs

13Hrs/20Hrs 14Hrs/20Hrs 26Hrs/38Hrs

4A 8Hrs/NA

10Hrs/NA

14Hrs/NA 15Hrs/NA 28Hrs/NA

5A 9Hrs/NA

12Hrs/NA

15Hrs/NA 17Hrs/NA 32Hrs/NA

6A

10Hrs/NA 16Hrs/NA 18Hrs/NA 22Hrs/NA 38Hrs/NA

Maintenance

The power supply and stand by battery(s) should be tested at least once a year as follows:

1. Check LEDs for normal state. AC ON Green, Output ON Yellow, DC ON Red.
2. Check output voltage with normal load. The AQU126-4F should read between 13.60 and 13.85vdc. The

AQU243-4F (&-8F) should read between 27.20 and 27.7vdc. This assures proper voltage to float charge
batteries.

3. With normal load, disconnect AC input. AC LED should be off, all other LEDs should remain normal.
4. Check DC Output to be above 12.1vdc for AQU126-4F and 24.2vdc for AQU243-4F. This checks standby

batteries to be operational. Sealed lead acid batteries have a typical life of 3 to 5 years.

5. Re Apply AC and verify AC LED ON.