SECURITRON MODEL RB4-12, RB4-24 RELAY BOARD

INSTALLATION AND OPERATING INSTRUCTIONS

1. DESCRIPTION
The RB4 board mounts four double pole, double throw relays with connection points to the coils
and contacts being implemented on screw terminals. The boards are furnished on Snap Trak

mounting permitting their installation in a variety of situations. The relays provide 2 Amp
contacts on each pole. The 12 volt version of the board uses relays that draw 13 mA each and
the 24 volt version uses relays that draw 8 mA each. The relays operate on DC only but will
accept +50%, -25% of nominal voltage. Pulsating DC (transformer + bridge rectifier) will
operate the relays. According to the status of jumper wires, the relays may be operated with

one side of their coils in common or they may be fully isolated from each other.

2. WIRING
Figure 1 shows terminal identification. As factory delivered with the four wire jumpers in place,
the “negative” coil terminals (-1, -2, -3, -4) are all in common. So to operate the relays, simply

apply 0 DC (negative) to any of the “-” coil terminals and then individually apply +DC to each
“+” coil terminal to operate the respective relay. Note that the relays are not polarized so
you can reverse this scheme if desired. +DC can be applied to any of the “-” coil terminals
and then the relays can be individually operated by applying 0 DC (negative) to each “+”
terminal.

RELAY 1 RELAY 2 RELAY 3 RELAY 4

NC1 NC2

NC2

NC2

NC2

NC1

NC1

NC1

NO1 NO2

C1

C2

C1

C1

C1

C2

C2

C2

NO1

NO1

NO1

NO2

NO2

NO2

COIL

INPUTS

CONTACTS

DC

1A

1B

2A

3A

4A

2B

3B

4B

1A

1B

2A

3A

4A

2B

3B

4B

1A

1B

2A

3A

4A

2B

3B

4B

+1

-1

+2

+3

+4

-2

-3

-4

JUMPERS

#1

#2

#3

#4

FIGURE 1: RB-4 WIRING

The four wire jumpers are normally left connected but may be cut for a special requirement.
In some applications, the voltage inputs that switch on the relays may be from more than one
power supply and you will not want to mix the supply voltages by putting them in common.

When the associated jumper is cut, the coil terminals are totally isolated. Therefore
different power sources can independently operate each relay, if desired.