Location of extrol, Expansion tanks, Point of connection – Amtrol EXTROL 500 LBC User Manual

Page 2: Installation, Please read the following instructions carefully, Operational limits, Operating instructions

Advertising
background image

PoTABLE WATEr ANd rAdIANT HEATING

WArNING. THIS ProdUCT MUST NoT BE

USEd IN rAdIANT HEATING, PoTABLE WATEr or oPEN SYSTEMS

oF ANY KINd. THESE SYSTEMS CoNTAIN oXYGENATEd WATEr

WHICH WILL CAUSE INTErNAL CorroSIoN ANd PrEMATUrE

ProdUCT FAILUrE. USE A THErM-X-TroL

®

For PoTABLE

WATEr SYSTEMS ANd A rAdIANT EXTroL

For rAdIANT

HEATING SYSTEMS. MoUNT VErTICALLY oNLY. do NoT INSTALL

oN dEAd-ENd PIPE

.

NOTE: INSPECT For SHIPPING dAMAGE ANd NoTIFY FrEIGHT

CArrIEr or STorE WHErE PUrCHASEd IMMEdIATELY IF

dAMAGE IS PrESENT. To AVoId rISK oF PErSoNAL INJUrY

ANd ProPErTY dAMAGE, IF THE ProdUCT APPEArS To BE

MALFUNCTIoNING or SHoWS SIGNS oF CorroSIoN, CALL A

QUALIFIEd ProFESSIoNAL IMMEdIATELY. CUrrENT CoPIES oF

THE ProdUCT MANUAL CAN BE VIEWEd AT WWW.AMTroL.CoM.

USE ProPEr SAFETY EQUIPMENT WHEN INSTALLING.

FAILUrE To ProPErLY SEAL WILL rESULT

IN LoSS oF PrECHArGE CAUSING ProdUCT

To FAIL.

GENErAL SAFETY INForMATIoN -

AddITIoNAL SPECIFIC SAFETY ALErTS

APPEAr IN THE FoLLoWING INSTrUCTIoNS.

CALIForNIA ProPoSITIoN 65 WArNING:

THIS ProdUCT CoNTAINS A CHEMICAL

KNoWN BY THE STATE oF CALIForNIA To CAUSE CANCEr ANd

To CAUSE BIrTH dEFECTS or oTHEr rEProdUCTIVE HArM.

(CALIForNIA INSTALLEr/CoNTrACTor - CALIForNIA LAW

rEQUIrES THAT THIS NoTICE BE GIVEN To CoNSUMEr/ENd USEr

oF THIS ProdUCT.) For MorE INForMATIoN: WWW.AMTroL.

CoM/ProP65/HTM.

Location of EXTroL

®

Expansion Tanks

do NoT LoCATE THIS ProdUCT WHErE

LEAKING or FLoodING CoULd CAUSE

dAMAGE To THE SUrroUNdING ProPErTY.

The AMTROL

®

expansion tank may be placed in any convenient position

within the mechanical room (or building). If multiple tanks are installed,

they should all be on the same level.

Point of Connection

Unlike a conventional tank, the EXTROL

®

sealed air cushion does not

require replenishment so DO NOT connect to an air separator or other air

collection device.
As with any expansion tank, it is recommended that the EXTROL

®

be

connected to the suction side of the pump. This will prevent the pump

head from becoming subtractive which may result in entry of air and vapor

formation at high points in the system.
By connecting the EXTROL

®

on the boiler return, displacement of coolest

system water into tank is ensured reducing energy waste.
Low pressure drop components such as air separators and boilers may be

placed between point of connection and pump suction if desired. System

design will dictate the feasibility of this.
Natural convection losses and the entry of air into tanks are eliminated by

connection to the side or underside of main pipe. The piping should be pitched

up and away from the EXTROL

®

to eliminate any potential air traps.

Installation

THIS ProdUCT MUST BE INSTALLEd BY A
QUALIFIEd ProFESSIoNAL.

1.

Note location of system connection, air charge valve and drain

connection on tank.

2. Remove the plug or pipe cap from the system connection.
3. Remove the 1 1/2” NPT plug covering the air charge valve.
4. Before making any connection to the tank, check the tank and air charge

(use an accurate pressure gauge). The air pressure must be equal to

the minimum system pressure at the tank location.

5. After making sure the air charge is correct, replace the 1 1/2” plug over

the air valve.

PLEASE rEAd THE FoLLoWING INSTrUCTIoNS CArEFULLY

6. The EXTROL

®

may now be piped to the system (use the suggested

EXTROL

®

piping diagrams on the next page).

7. Using the table below, select appropriate pipe size. Connection to

each EXTROL

®

must have a lock shield gate valve and union to allow

isolation and removal if required. Make up and fill valves, whether

manual or automatic, should be tied into the connecting line. This will

ensure that pump operation will not affect valve operation.

operational Limits

Maximum Operating Pressure: As stamped on nameplate
Maximum Operating Temperature: 240 °F
Minimum Operating Temperature: 35°F (non-glycol application)
If unit is being installed in a glycol system where minimum temperatures

fall below 35°F, contact the AMTROL technical service department at

(401) 535-1216.

operating Instructions

1. Check the expansion tank pre-charge before the system is filled with

water. The charge is 12 psig unless noted otherwise on the tank label.

Check to make sure this is the correct pre-charge pressure specified

for the system.

2. If the tank pre-charge pressure needs to be changed on a dry system

follow the following procedure:

a.

Check the expansion tank air pressures at the pre-charge

connection with an accurate tire type pressure gauge. The

pre-charge connection is the same kind of connection found on

automobile tires.

b. If the pressure is low, charge the tank with nitrogen gas or with

oil free compressed air. Check the pressure frequently during this

process as you would when filling a tire with air.

3. If, after the system has been filled with water and operating, it is

found that the expansion tank pre-charge must be changed use the

following procedure:

a. Turn off the heat source and allow the system water to cool to

ambient temperature.

b. Close the lock-shield valve in the tank-to-system piping.
c. Open the drain valve to empty the water from the tank.
d. Check the tank air pressure at the pre-charge connection with an

accurate tire type air gauge.
e. Refer to 2b above.
f. Close the drain valve, open the lock-shield valve and turn on the

heat source.
g. Relock the lock-shield valve.

Firing rate

Length of Pipe Connecting

of Boiler

Tank to System:

MBTU/H

Below 11’

11’ – 30’

31’ – 100’

2,000

1/2”

3/4”

1”

4,000

3/4”

1”

1 1/4”

8,000

1”

1 1/4”

1 1/2”

12,000

1 1/4”

1 1/2”

2”

16,000

1 1/4”

2”

2 1/2”

20,000

1 1/2”

2”

2 1/2”

dANGEr: Excessive pressure can cause tank to explode.

Exercise care when filling a tank with air so the pressure

does not exceed that required or does not exceed the

working pressure of the tank as stamped on the nameplate.

Failure to follow these instructions will result in serious personal

injury or death and property damage.

IMPorTANT: Expansion tank cannot be properly

air charged other than at ambient temperature.

Advertising