HOCHIKI YBN-R/3(SCI) SHORT-CIRCUIT ISOLATOR
BASE INSTALLATION INSTRUCTIONS

General Description

The YBN-R/3(SCI) is a sensor mounting base featuring an integral short-circuit isolator which
will detect and isolate short-circuits on the loop. When a short-circuit is detected during power up the unit will drop
the power to the rest of the loop.

The YBN-R/3(SCI) is compatible with the ESP range of sensors (see compatibility chart below). The unit does not
require a loop address. A remote fire LED facility is provided when a sensor is attached to the base.

Note:- A fitted sensor will still be powered when this device is isolating.

Specifications

Ordering code

YBN-R/3(SCI)

Protocol ESP
Operating Voltage

17 - 41 V dc (24 V dc nominal)

Standby current

60 µA

Current drawn by isolator during fault condition

< 4 mA

Maximum current consumption from remote LED

10 mA (limited by attached sensor)

Maximum continuous current

1 A

Maximum quantity per loop

127*

1

Ambient temperature range

-10

C to +50 C

Relative humidity

10% to 95% RH (at 40

C)

Colour and case material

Ivory or White ABS

Fixing centres

48 mm through to 74 mm

Maximum wire thickness

2.5 mm²/terminal

Weight 79

g

*

1

Check with Fire alarm control panel manufacturer for

maximum loop quantities

See AP0127 for short-circuit isolator specifications

Compatibility

The YBN-R/3(SCI) isolator base has been designed to work with the sensors listed below. All sensors are
compatible with Hochiki ESP (Enhanced System Protocol).

Sensor Type

Ordering Code

Photoelectric (smoke) sensor

ALG-E, ALG-EN, ALK-E, ALN-E (and all variants)

Ionisation (smoke) sensor

AIE-E (and all variants)

Temperature (heat) sensor

ATG-E, ACB-E, ATJ-E (and all variants)

Multi (smoke and/or heat) sensor

ACA-E, ACC-E (and all variants)

Precautions

Ensure that this device is installed in accordance with local standards or regulations.

Only install in suitable environments, the following should be avoided : -

Excessive ambient temperature.

Where excessive condensation or moisture is present.

Hazardous areas.

Do not use a high voltage tester on these devices.

Ensure that the YBN-R/3(SCI) base isolator is securely fixed to the ceiling or other suitable surface.

Ensure that the terminals on the unit are securely fastened.

When fitting the YBN-R/3(SCI) isolator base, for proper wiring supervision, ensure that the cables are routed
through the base terminals and not spurred off a main wiring route.