Hochiki YBO-R/SCIM User Manual

General description, Ybo-r/sci & ybo-r/scim isolator base, Specifications

Advertising
background image

2-3-0-367/ISS6/OCT13

HOCHIKI YBO-R/SCI & YBO-R/SCIM SHORT CIRCUIT
ISOLATOR BASES & CHQ-SCI/DIN SHORT CIRCUIT
ISOLATOR MODULE

INSTALLATION INSTRUCTIONS

General Description

These devices detect and isolate short-circuits on the loop. When a short-circuit is detected during power up these
isolators will illuminate their integral LED (yellow) and drop the power to the rest of the loop.

YBO-R/SCI & YBO-R/SCIM Isolator Base

The YBO-R/SCI (and the marine-approved equivalent YBO-R/SCIM) is a short-circuit isolator combined in a base
compatible with the ESP range of sensors (see compatibility chart below). The Isolator can also be used as a stand
alone unit with the addition of a simple clip on cover (SI/CAP), in either configuration the unit does not require a loop
address. A remote fire LED facility is provided when a sensor is attached to the base.

Note:- If a sensor is fitted this will still be powered when the device is isolating (yellow LED illuminated).

Specifications

Base Isolator

Ordering codes

YBO-R/SCI *

1

YBO-R/SCIM (Marine-Approved)

Protocols

ESP/HRE

#

Operating Voltage

19-41 Vdc (24 Vdc nominal)

Standby current

60 µA

Current drawn by isolator during fault condition

< 10 mA

Maximum current consumption from remote LED

N/A

Maximum continuous current

1 A

Maximum quantity per loop

127*

2

LED colour

Yellow

Ambient temperature range

-10

C to +50

C

Relative humidity

10% to 95% RH

(at 40

C)

Colour and case material

Ivory or White ABS

Fixing centres

48 mm through to 74 mm

Maximum wire thickness

2.5 mm²/terminal

Weight

92g

Optional cover for stand alone use

SI/CAP

NOTE: See AP0127 for short-circuit isolator specifications

#

The YBO-R/SCI can be used on the HRE protocol as a replacement for the SCI/2a, but as a stand alone isolator only, in other words, with

no sensor fitted.

*

1

Fire alarm control panel compatibility is required for this product.

*

2

Check with Fire alarm control panel manufacturer for maximum loop quantities

Compatibility

The YBO-R/SCI base isolator has been designed to work with the sensors listed below. All sensors are compatible
with Hochiki ESP (Enhanced System Protocol).

Sensor Type

Ordering Code

Photoelectric sensor

ALG-E, ALG-EN, ALK-E (and all variants)

Ionisation sensor

AIE-E (and all variants)

Temperature sensor

ATG-E, ACB-E, ACB-EW (and all variants)

Multi-Sensor

ACA-E

Advertising