Wiring – Hochiki SLR-E3N User Manual

Page 2

Advertising
background image

2-3-0-500/ISS10/NOV09

Wiring

The wiring diagram for the conventional detector base should be made as shown.

A: Zone (+) B: Zone (-) C: Cable Screen

*The Schottky Diode Bases can easily be converted into non-Schottky versions by removing the Schottky diode, which is fitted between terminals 1 and 2.

**The Schottky Diode Bases can easily be converted into non-Schottky versions by cutting out and removing the Schottky diode, which is soldered on the
underside between terminals 1 and 2.

Note

The YBO-R/6RN base will automatically reset the detector every 8 - 15 seconds after it has entered an alarm
state. If the detector remains above its alarm threshold after a reset the LEDs will illuminate again. This will
continue until a reset is achieved. The relay contacts (and Remote Indicator) will not change state until the reset
is successful.

DCD-AE3

0832-CPD-0116

05

EN54-5 Point type heat detectors

DCD-CE3

0832-CPD-0117

05

EN54-5 Point type heat detectors

DFJ-AE3

0832-CPD-0118

05

EN54-5 Point type heat detectors

DFJ-CE3

0832-CPD-0119

05

EN54-5 Point type heat detectors

SLR-E3

0832-CPD-0111

05

EN54-7 Point type smoke detectors

SLR-E3N

0832-CPD-0614

08

EN54-7 Point type smoke detectors

YBO-R/6R

0832-CPD-1112

09

EN54-18 Input/Output modules

YBO-R/6RS

0832-CPD-1113

09

EN54-18 Input/Output modules

Protocol specified in TI/006

YBO-R/6RN

0832-CPD-1114

09

EN54-18 Input/Output modules

Hochiki Europe (UK) Ltd
Grosvenor Road, Gillingham Business Park,
Gillingham, Kent, ME8 0SA, England Telephone:
+44(0)1634 260133 Facsimile: +44(0)1634 260132
Email: [email protected]
Web: www.hochikieurope.com

Hochiki Europe (UK) Ltd. reserves the right to alter the
specification of its products from time to time without notice.
Although every effort has been made to ensure the accuracy of
the information contained within this document it is not warranted
or represented by Hochiki Europe (UK) Ltd. to be a complete and
up-to-date description. Please check our web site for the latest
version of this document.

Note: When
using older
variants of
those mounting
bases listed
overleaf, the
three locating
tabs on the
SLR-E3N will
need to be
carefully
removed with
pliers.