Hochiki CHQ-SZM/M(SCI) User Manual

Page 2

Advertising
background image

Hochiki Europe (UK) Ltd

Page 2

2-3-0-778/ISS8/DEC11

CHQ-DIM - DUAL INPUT MONITOR
This device is a loop-powered module designed to interface to a variety of inputs,
such as, door contacts, sprinkler flow/door switches and plant equipment fault
contacts, this module is particularly suited to applications where a fast response is
required to the input change.

Setting Contact Monitoring
Both volt free input contacts can be configured to be either N/O or N/C, by setting the
2-bit DIL switch

CHQ MODULE

SWITCH 1 UP

I/P 1 Normally Closed (N/C)

SWITCH 1 DOWN I/P 1 Normally Open (N/O)
SWITCH 2 UP

I/P 2 Normally Closed (N/C)

SWITCH 2 DOWN I/P 2 Normally Open (N/O)

DIN MODULE

SWITCH 1 UP

I/P 1 Normally Open (N/O)

SWITCH 1 DOWN I/P 1 Normally Closed (N/C)
SWITCH 2 UP

I/P 2 Normally Open (N/O)

SWITCH 2 DOWN I/P 2 Normally Closed (N/C)

LOOP CONNECTIONS: S = Cable Screen (if required), - = Loop Negative (-ve), + = Loop Positive (+ve)
Order codes

CHQ-DIM(SCI) / CHQ-DIM/M(SCI) / CHQ-DIM/DIN(SCI)*

1

Transmission method

Digital communication using ESP

Operating voltage

17 - 41 VDC

Quiescent current

280

A

Current in short-circuit

8 mA

Current consumption whilst polling

22 mA

 20 %

Maximum short-circuit current (Loop) 1

A

Current consumption with inputs active 4.3 mA (Both active)*

2

Input line resistance

ON threshold <50

, OFF threshold >100 K

Weight (g) &
Dimensions (mm)

CHQ-DIM(SCI)
CHQ-DIM/M(SCI)

327

L157 x W127 x D35 (CHQ Module plus Lid)
D=79 (CHQ Module plus Lid plus CHQ-BACKBOX)
(add 235 to module weight when using CHQ-BACKBOX)
L108 x W119 x D24 (CHQ DIN Module)

CHQ-DIM/DIN(SCI) 113

Colour and enclosure material

CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS

*

1

Fire alarm control panel compatibility required for these products.

*

2

Note: - Add 85

A per input for normally closed contact monitoring

CHQ-DZM - DUAL ZONE MONITOR
This device is an externally powered module designed to allow up to 60
conventional detectors (30 per zone) to be interfaced to Hochiki’s ESP analogue
addressable system. The unit features three End Of Line (EOL) monitoring options
(see page 3 for further details).

Setting EOL Monitoring Option
Select the required EOL monitoring option using the 2-bit DIL switch.

CHQ MODULE

SWITCH 1 DOWN

ZENER

SWITCH 2 DOWN
SWITCH 1 UP

ACTIVE/RESISTIVE

SWITCH 2 DOWN

DIN MODULE

SWITCH 1 UP

ZENER

SWITCH 2 UP
SWITCH 1 DOWN

ACTIVE/RESISTIVE

SWITCH 2 UP

LOOP CONNECTIONS: S = Cable Screen (if required), - = Loop Negative (-ve), + = Loop Positive (+ve)
Order codes CHQ-DZM(SCI) / CHQ-DZM/DIN(SCI)

Transmission method

Digital communication using ESP

Operating voltage

17 - 41 VDC

Low Power Mode (typ)

110

A

Resistance on Zone (max)

50 Ω

Quiescent current (typ)

330

A

Capacitance on Zone (max)

0.3 µF

Current consumption (external)

(Quiescent) 2mA, (Alarm) 70mA (both zones in fire)

Current in short-circuit

8 mA

Maximum short-circuit current (Loop) 1 A

Output rating

24 VDC 8.5 mA

Detectors per zone

DCA, DFB, DFE – No limit, SLG, SLK, SLR, SIF, SIH, SIJ, DCC, DCD, DFJ – 30 max,
SPB-ET, SPC-ET or SRA-ET– Only one and no other detectors, HF-24 – Only one and no other detectors,
DRD-E – 15 max, Conventional Call Points – No limit

Weights (g) &
Dimensions (mm)

CHQ-DZM(SCI) 350

L=157 x W=127 x D=35 (CHQ Module plus Lid)
D=79 (CHQ Module plus Lid plus CHQ-BACKBOX)
(add 235 to module weight when using CHQ-BACKBOX)

CHQ-DZM/DIN(SCI) 130

Colour and enclosure material

CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS

*

1

Fire alarm control panel compatibility required for these options.

Fig 5

Fig 4

Advertising