Products covered: CHQ-DZM(SCI)-IS, CHQ-DZM/DIN(SCI)-IS

Function

The CHQ-DZM(SCI)-IS is an input monitoring device which connects to the Hochiki ESP analogue system. It is capable
of monitoring two zones of intrinsically safe detectors through an intrinsically safe barrier. The unit also provides two
controllable outputs, which can be used to drive remote LEDs (if supported by the Control Panel). The unit is available as
either a “Smart-Fix” module box or as a DIN Rail mountable unit with both variants featuring an integral short-circuit
isolator.

Specification

Order codes

CHQ-DZM(SCI)-IS and CHQ-DZM/DIN(SCI)-IS*

Transmission method

Digital communication using ESP

Loop

Operating voltage

17 – 41 VDC

Quiescent current

330 µA

Current consumption whilst polling

22 mA ± 20 %

Isolator leakage current (switch open)

8 mA (max)

Isolator switch current (switch closed)

1 A (max)

External
supply

Operating voltage

20-28.8 VDC (24 VDC nominal)

Current consumption when in fire

70 mA (Both zones in fire)

Output rating

24 VDC 8.5 mA

Zone loading (max)

Up to 20 SLR-E-IS or DCD-1E-IS detectors (or a mixture of
both), Up to 20 CCP-E-IS manual call points

E.O.L device (see note below)

10 k

 resistor

Zone resistance

50

 (Max)

Zone capacitance

0.3 µF (Max)

Colour and enclosure material

CHQ Module & CHQ-BACKBOX White ABS
DIN Module Green ABS

* Fire alarm control panel compatibility required for these products.

See AP0127 for short-circuit isolator specifications.

NOTE: The EOL resistors supplied with the CHQ-DZM(SCI)-IS comply with Hochiki’s BASEEFA certification for
conventional I.S. detectors. The user must check that any EOL resistors used comply with the certification requirements
for the proposed installation.

Components

Standard "Smart-Fix" Modules are supplied as two individual components (see Fig 1 & 2). DIN versions are supplied as one unit
(see Fig 3).

Fig 1

Fig 2

"Smart-Fix" CHQ Module (Back Plate inc PCB Component)

(Note: configuration of Wiring Terminal blocks differs between

models)

CHQ-LID Transparent Module Lid

(Supplied with four screws and acrylic retaining washers)

Advertising
This manual is related to the following products: