Installation – "smart-fix" version, Installation with back box – Hochiki CHQ-PCM(SCI) User Manual

Page 3

Advertising
background image

2-3-0-1156/ISS2/OCT11

Specification

Order codes

CHQ-PCM(SCI) (module)
CHQ-PCM/DIN(SCI) (DIN module)

Transmission method

Digital communication using ESP

Loop

Operating voltage

17 - 41 Vdc

Quiescent current

300

A

Current consumption whilst polling 22 mA

 20 %

Relay contact rating

30 Vdc max, 1 A (resistive load)

Input E.O.L resistor

10 k

, 5%, 0.25 W

Input threshold level

ON=470

, Short cct <50 , Open cct >100 K

Isolator

Switch current (switch closed)

1 A

Leakage current (switch open)

3 mA (max)

Weight (g)
Dimensions (mm)

CHQ Module

332

L157 x W127 x H35 (CHQ Module with lid),

567

H79 (CHQ Module with lid and CHQ-BACKBOX)

DIN Module

150

L119 x W108 x H24 (CHQ DIN Module)

Colour and enclosure material

CHQ Module & CHQ-BACKBOX white ABS, DIN Module green ABS

Fire alarm control panel compatibility is required for both variants of this product. See AP0127 for short-circuit isolator specifications.

Note:- All EOL and operational resistors are supplied with the unit – DO NOT DISCARD!

Installation – "Smart-Fix" Version

Set analogue address before installation (see page 1).
The fixing surface should be dry and stable.

Hold the back plate up against the fixing surface and
mark the position of the four corner fixing holes.

Determine which cut-out sections along the top and
bottom edges of the module require removing to
accommodate the cables being used.

Remove cut-outs by scoring with a sharp knife before
breaking off with pliers or snips.

Mount the back plate using appropriate fixings (not
supplied) for the fixing surface.

Terminate and connect field wiring as per the wiring
diagrams on pages 2 & 3 (and the terminal block
indications on the product label).

The transparent lid (CHQ-LID) is supplied with four screws
and eight retaining washers.

Push the screws through one of the retaining washers
and then through the holes in the lid from front to
back, pushing another retaining washer onto the end
inside the lid.

Screw the lid onto the back plate; do not over tighten
the screws as this could damage the unit.

NOTE: A white plastic version of the lid is available (sold
separately – CHQ-LID(WHT)).

Fig 5

Installation with Back Box

For installations requiring glanded cables, a module back box (CHQ-BACKBOX) is available (sold separately). This is
mounted on the fixing surface; the CHQ Module is then fitted to the top of the back box and the CHQ-LID is added creating
a sealed enclosure. For further details refer to the CHQ-BACKBOX Instructions (2-3-0-800). For CHQ-PCM installations
utilising heavy-duty cabling (for example, 1.5mm

2

solid conductor) the use of the SMB-1 Box with the SMB-ADAPTOR

plate and CHQ-ADAPTOR is recommended.

For further details refer to the SMB-ADAPTOR Instructions (2-3-0-1502).

Ensure

any glands used (not supplied) conform to IP67, if such ingress protection is required.