Hochiki CCP-E-IS User Manual

Page 2

Advertising
background image

2-3-0-563/ISS1/SEPT03

TESTING
To test the call point insert the supplied test key into the aperture at
the bottom of the unit, the glass will drop and simulate operation of
the call point (see Fig.4). To reset remove the key.

Fig. 4


Specification

Ordering Code

CCP-E-IS

Plastic Back Box Ordering Codes

SR2T (2 terminals) / SR3T (3 terminals)

Operating Voltage

15-30V

Resistor

470

Ω / 2.5W

Operating & Storage Temperature Range -30

°C to + 70°C

Maximum Humidity

95%RH - Non Condensing (at 40

°C)

Colour Red
Case Material

Nylon / Self-extinguishing Modified Polyphenelene
Oxide

IP Rating

IP24D
Flush Unit - L88 x H88 x D20 / 100

Dimensions (mm) / Weight (g)

Surface Box - L88 x H88 x D32 / 80

Maximum Wire Thickness

2.5mm