Hochiki IFD-E User Manual

Page 10

Advertising
background image

10

Hochiki Europe (UK) Ltd

2-3-0-808/ISS3/OCT11

Detector Supply Current
i
@ 24Vdc

DIL Switch

Setting

Comment

Normal

Quiescent

Current

Alarm

(Fire) Current



1



2



3



4

3mA

9mA

0 0 0

0

Lowest power configuration,
RL1 only

4mA

20mA

0

0

1

0 For 4-20mA systems, no relays

8mA

14mA

1 1 0

0

Lowest power configuration &
relays

8mA

20mA

1

1

0

1 For 4-20mA systems & relays

8mA

28mA

1 1 1

1 Fire

control

panels

Table 4 Detector Supply & Alarm Currents

If the detector supply current falls below the normal quiescent current consumption then a fault is present.
This could be simply an open circuit cable fault or a fault within the detector possibly due to the detector
being taken over its rated temperature.

Detectors can be connected in parallel increasing the overall quiescent current required. The alarm
current signal will remain the same with the additional quiescent current drawn from other detectors.

Fig 9

Basic 4 Wire Connection Diagram

NOTE 1

Screened cable should be used with one end of the screen connected to earth. Also care should be
taken not to run the detector cable next to power cables.

NOTE 2

R = To indicate fire to control unit or interface.
For example, 470R

NOTE 3

EOL = End of line device required by some
control units. This is required to monitor the
cable to the detectors and prevent fault
indications on the control unit.