Place the water heater in such a manner that the air filter, cover, and front panels can be removed to permit inspection and servicing,
such as removal of elements or cleaning of the filter.

The water heater and water lines should be protected from freezing temperatures and highly corrosive atmospheres. Do not install the
water heater in outdoor, unprotected areas.

The water heater should not be located in an area where leakage of the tank or connections will result in damage to the area adjacent
to it or to lower floors of the structure. Where such areas cannot be avoided, it is recommended that a suitable, adequately drained
catch pan be installed under the water heater.

Figure 2

– Catch Pan Detail

This water heater SHOULD NOT be installed in a space where liquids which give off flammable vapors are used or stored. Such liquids
include gasoline, LP gas (butane and propane), paint or adhesives and thinners, solvents, or removers. Because of natural air
movement in a room or other enclosed space, flammable vapors can be carried from where flammable liquids are being used or stored.
The operation of the control system within the water heater can ignite these vapors, causing an explosion or fire which may result in
property damage, as well as potentially severe burns or death to those in range.

Figure 3

– To facilitate condensate drainage and proper operation, ensure the water heater is installed level.

B. REQUIRED CLEARANCES

In the event service is needed, there must be AT LEAST 16

” top, 12” sides, and 7” minimum clearance (air space) between any object

and the front and rear covers.