If an in-line high gas pressure regulator is used, it must be installed a minimum of 10 feet from the boiler. It is very important
that the gas line is properly purged by the gas supplier or utility. Failure to properly purge the lines, or improper line sizing,
will result in ignition failure.
This problem is especially noticeable in NEW LP installations and empty tank situations. This situation
can also occur when a utility company shuts off service to an area to provide maintenance to their lines. This gas valve must not be
replaced with a conventional gas valve under any circumstances.

DO NOT adjust or attempt to measure gas valve outlet pressure. The gas valve is factory-set for the correct outlet pressure and
requires no field adjustment. Attempts by the installer to adjust or measure the gas valve outlet pressure could result in damage to the
valve and cause substantial property damage, severe personal injury, or death.

D. GAS VALVE

Figure 28

– LP-171-N

Do not do a gas conversion on this boiler without an officially approved conversion kit and instructions supplied by HTP. Failure to use a
conversion kit when converting the boiler to fire on Natural or LP gas will result in extremely dangerous burner operation, leading to fire,
explosion, severe injury or death.

Strain on the gas valve and fittings may result in vibration, premature component failure and gas leakage, and result in fire, explosion,
property damage, severe personal injury, or death.

Adjustments to the throttle screw or offset may only be made by a qualified gas technician using a calibrated combustion analyzer
capable of measuring CO

2

and CO. Failure to follow this instruction could result in fire, explosion, property damage, severe personal

injury, or death.