PART 9 – SHUTDOWN

A. SHUTDOWN PROCEDURE

If the burner is not operating, disconnect the electrical supply.

If the burner is operating, lower the set point value to 70

o

F and wait for the burner to shut off. Continue

to wait for the combustion blower to stop, so all latent combustion gases are purged from the system.
This should take a maximum of 40 to 90 seconds.

B. VACATION PROCEDURE

If there is danger of freezing, change the set point to 70

o

F. DO NOT turn off electrical power. If there is

no danger of freezin

g, follow “Shutdown Procedure”.

C. FAILURE TO OPERATE

Should the burner fail to light, the control will perform two more ignition trials prior to entering a lockout
state. Note that each subsequent ignition trial will not occur immediately. After a failed ignition trial, the
blower must run for approximately 10 seconds to purge the system. Therefore, a time period of
approximately 40 to 90 seconds will expire between each ignition trial.

If the burner lights during any one of these three ignition trails, normal operation will resume. If the
burner lights, but goes off in about 4 seconds, check the polarity of the wiring. See electrical connection
section.

If the burner does not light after the third ignition trial, the control will enter a lockout state. This lockout
state indicates that a problem exists with the water heater, the controls, or the gas supply. Under such
circumstances, a qualified service technician should be contacted immediately to properly service the
water heater and correct the problem. If a technician is not available, depressing the

{S4}

button once

will remove the lockout state so additional trials for ignition can be performed. The unit will try to re-light
once every 6 minutes.

PART 10 – TROUBLESHOOTING

A. ERROR CODE

An error code may occur during installation of the heater. This condition may lead to a lock out condition of the controller, which will
need to be manually reset by pressing the

{S4}

button. These following will help the installer correct the problem before going into a

lock out condition, which will require a manual reset.

B. HEATER ERROR

1. When an error condition occurs the controller will display an error code on the display module.

2. These error codes and several suggested corrective actions are included in Table 14.

3. In the case of

|E00|

,

|E13|

, and

|E14|

this error, if uncorrected, will go into a fault condition as described in Paragraph C.

C. LOCKOUT

1.

When a fault condition occurs the controller will illuminate the red “fault” indication light and display a fault code in the format

(Example:

|F00|

) on the display module.


2. Note the fault code and refer to Table 15 for an explanation of the fault code along with several suggestions for corrective actions.

3. Press the reset key to clear the fault and resume operation. Be sure to observe the operation of the unit to prevent a recurrence of
the fault.

When servicing or replacing any components of this water heater be certain that:

The gas is off.

All electrical power is disconnected.



RESISTANCE TABLE FOR

SUPPLY TEMPERATURE

SENSOR

HIGH/LOW

TEMP.

SENSOR

TEMP. (

o

F)

RESISTANCE

(ohms)

32

32550

41

25340

50

19870

59

15700

68

12490

77

10000

86

8059

95

6535

104

5330

113

4372

122

3605

131

2989

140

2490

149

2084

158

1753

167

1481

176

1256

185

1070

194

915

202

786

212

667

Table 13