1 explanation of i/o signals, 2 details of input signals – IAI America ERC User Manual

Page 50

Advertising
background image

30

3.4.1 Explanation of I/O Signals


The following explains the signals used in the “8 points” and “16 points” patterns.

Category

Signal name

Signal

abbreviation

Function overview

Start

CSTR

Movement of the actuator starts at the rise edge of this signal.

Command

position number

PC1

PC2

PC4

PC8

This signal is used to input a position number that specifies movement.

Be sure to set a command position number by 6 ms before the start signal

(CSTR) is turned ON.

*Pause

*STP

ON: The actuator can be moved, OFF: The actuator decelerates to a stop

Input

Home return

HOME

Home return starts at the rise edge of this signal.

Position complete

PEND

This signal turns ON when the actuator has moved close enough to the target

position and entered the in-position band.

Used to determine if positioning has completed.

Home return

completion

HEND

This signal turns OFF when the power is input, and turns ON when home

return completes.

Zone ZONE

This signal is output if the current actuator position is within the range set by

the parameter upon completion of home return.

Used as a limit switch for an intermediate point or a simple ruler for push &

hold operation.

Output

*Alarm *ALM

This signal remains ON while the controller is operating properly, and turns

OFF when an alarm generates. The *ALM signal is synchronized with the

green/red indication of the LED.

(Note) The signal remains ON while the motor drive power is cut off.

3.4.2 Details of Input Signals


The input signals from this controller have an input time constant, in order to prevent malfunction caused by
chattering, noise, etc.
Each input signal will switch the applicable setting when received continuously for 6 msec or more.
In other words, when a given input is switched from OFF to ON, the controller will recognize the ON state of the
signal only after elapse of 6 msec.
The same applies to the switching of an input from ON to OFF. (Fig. 1)








Fig. 1 Recognition of Input Signal

Start (CSTR)

When the OFF

 ON rise edge of this signal is detected, the controller will read the target point number as the

3-bit binary code consisting of signals PC1 to PC4 (or 4-bit code consisting of signals PC1 to PC8 if the “16
points” pattern is selected), and perform positioning to the target position specified by the corresponding position
data.

6 [msec]

6 [msec]

Input signal


Recognition by the controller

Not recognized

Not recognized