26

3. Installation and W

iring

3.8.2

Cutting Off the Motor Drive Power

If the motor drive power must be cut off in order to meet the required safety category of the entire system, connect
external EMG relay contacts between the MPI terminal and MPO terminal.
Also connect the 24-V controller power supply to the EMG terminal.

(Note) The EMG switch on the teaching pendant cuts off the motor driver signal. It does not cut off the motor drive

power.

For driving the motor
These lines are
shorted internally.

For driving the motor
These lines are
shorted internally.

For driving the motor
These lines are
shorted internally.

24-VDC control
power supply

External EMG
reset switch

External EMG circuit

Relay

Power-supply

terminal block (1st)

Power-supply

terminal block (2nd)

24-VDC input power
supply
(Max. 2 A per unit)

Power-supply

terminal block (3rd)

24-VDC input power
supply
(Max. 2 A per unit)

24-VDC input power
supply
(Max. 2 A per unit)

0 VDC