3-2-5 Hold

Input


This is used for temporary stop. The actuator will hold according to the external input signal (Hold) during moving.
Based on safety compliance, the signal will become a B-contact input (reversed logic). When the hold input is
turned OFF, the actuator will stop at that point and will move again only when the hold input is turned back ON.











The remaining movement of the actuator can be cancelled by turning the reset input ON while the hold signal is
being input (at the leading edge of the reset input signal).

















3-2-6 Zone Signal Output

During transfer, the zone signal is output once the actuator is inside the specified territory (this territory can be
set between desired positions).

By setting the zone parameter beforehand, once a moving slider enters that territory, the zone signal output turn
ON. (The territory can be set even in the middle of the stroke.)












Hold Input Signal



Reset





Actuator Movement

Zone signal ON

Zone signal setting range