Specifications – JuiceGoose NXRT Series User Manual

Page 31

Advertising
background image

NXRT‐1000, NXRT‐1500, NXRT‐2000, NXRT‐3000 USER’S MANUALUNINTERRUPTIBLE POWER SUPPLY (UPS) 

SPECIFICATIONS 

120V MODEL

NXRT-1000

NXRT-1500

NXRT-2000

NXRT-3000

INPUT

Voltage

120 VAC (80 - 138V at 100% load) 60-138V at 40% load

Capacity VA (W)

1000 VA (700 W)

1500 VA (1050 W)

2000 VA (1400 W)

3000 VA (2100 W)

Frequency

50/60 Hz auto sensing

Power Factor

≥ 0.97

Topology

True on-line, Double conversion, Input PF correction

OUTPUT

Voltage 120

VAC

Frequency

50/60 Hz auto sensing

THD (full load)

Linear ≤ 5%; non-Linear ≤ 10%

Wave Form

Sine wave, zero transfer time

Load Power Factor

0.7

Efficiency AC/DC/AC

≥90%

Auto Restart

Yes

Start on Battery

Yes

Rated Current

8.3 A

12.5 A

16.6 A

25 A

Overload Capacity

110-150% for 30 sec, ≥ 150% for 200 msec

Crest Factor

3:1 at full load

BATTERY

Battery Type (UPS)

(3) 12V 9 AH / 36V

(4) 12V 7.2 AH / 48V

(8) 12V 7.2AH / 96V

Backup Time

7-11 min (internal batteries) to 18 hours using External Battery Packs (EBP)

Extended Battery Packs

EBP1

EBP2

EBP3

Battery Type (EBP)

2 strings of (3) 12V

9 AH / 36V

2 strings of (4) 12V

7.2 AH / 48V

2 strings of (8) 12V 7.2 AH / 96V

Recharge Time

< 8 hours to 90%

 [31] 