Installation, Save these instructions, Danger – King Electric Model EKB User Manual

Page 4: Wire and breaker sizing

Advertising
background image

Installation

4

Model

Volts Watts Amps

Wire

Breaker size

EKB2450 240 5000

20

10-2 w/ground 30 Amp 2 pole

EKB2050 208 5000

24

10-2 w/ground 30 Amp 2 pole

EKB2440 240 3850

16

12-2 w/ground 20 Amp 2 pole

EKB2040 208 3750

18

10-2–w/Ground 30 Amp 2 pole

EKB2430 240 2850

12

14-2 w/ground 15 Amp 2 pole

EKB2030 208 2850

14

12-2 w/ground 20 Amp 2 pole

EKB1230 120 2850

24

10-2 w/ground 30 amp 1 pole

EKB1220 120 1920

16

12-2 w/ground 20 amp 1 pole

Wire and Breaker sizing

The wire and breaker sizing chart will give a general rule of installation
size. If you have long distance wire runs, larger size wire is required
due to voltage drops. Consult an electrician if you are not knowledgea-
ble about wiring codes.

Wiring
Branch Circuit Connection
1. Connect heater only to the voltage, amperage and frequency

specified on the nameplate.

2. Wiring procedures and connections shall be in accordance with all

National and local codes having jurisdiction.

3. Removing the two screws on the bottom of the heater will allow

you to gain access to the wiring compartment.

4. A knock of 1/2 inch (12.7 mm) conduit size (7/8 inch) is provided

in the back of the heater for power to enter. Provide proper con-
duit connectors for your flexible connections.

5. Wires will be placed in the terminal block lugs labeled L1 and L2

and tightened to 35 lbs. of torque. Lugs are approved for copper
or aluminum conductors from # 14 to #2 AWG. Minimum 600 volt
60 degree C wire is required. Copper wire is recommended. Fig.
4.2

6. Attach ground to the green wire with a wire nut.
7. Assemble all covers on electrical and apply power. Test unit by

turning thermostat up past room temperature. You will see a puff

of smoke as the elements are energized and the fan turns on. This
is a normal burn off of manufacturing lubricants and will dissapate
in 5 minutes.

8. Heater will continue to run until the room temperature you set is

reached and then turn itself off until the temperature drops again.

9. CAUTION - High temperature. Risk of fire, keep electrical

cords, drapery, furnishings, and other combustibles at least 3 feet
(0.9 m) from the front of the heater as well as away from the side
and rear. To reduce the risk of fire, do not store or use gasoline or
other flammable vapors and liquids in the vicinity of the heater.



Other manufacturing options to add to EKB
Pilot light– Add Suffix -P
Circuit breaker– Add Suffix -CB
Disconnect switch -Add Suffix -DS

Add Suffix to end of EKB model number

ELECTRIC SHOCK OR FIRE HAZARD

DANGER

!

!

Fig 4.1

SAVE THESE INSTRUCTIONS

CAUTION!

Turn off all electrical power to install wiring

Rating Label on back of heater

Fig 4.0

Fig 4.2

King Electrical Mfg. Co. 9131 10th Ave So. Seattle, Wa 98108 206-762-0400 www.king-electric.com