Technical data, 480vac models, 600 vac models – LEESON SM4 Series Flux Vector User Manual

Page 8: Stop, Drive derating, Type power [hp/kw] mains output current, Voltage, Clim

Advertising
background image

7

Technical data

480VAC Models

Type

Power

[Hp/kW]

Mains

Output Current

SM2

Watts

Loss

SM4

Watts

Loss

Voltage

(1)

I

in

I

n

CLim

max

(2)

400V

480V

400V

480V

400V

480V

174620-174671

0.5 / 0.37

400 V Three-phase (3/PE)

(340 … 440 V)

OR

480 V Three-phase (3/PE)

(340 … 528 V)

1.7

1.5

1.3

1.1

175

200

23

21

174621-174672

1 / 0.75

2.9

2.5

2.4

2.1

175

200

37

33

174622-174673

1.5 / 1.1

4.2

3.6

3.5

3.0

175

200

48

42

174623-174674

2 / 1.5

4.7

4.1

4.0

3.5

175

200

57

50

174624-174675

3 / 2.2

6.1

5.4

5.5

4.8

175

200

87

78

174625-174676

5 / 4.0

10.6

9.3

9.4

8.2

175

200

128

103

174626-174677

7.5 / 5.5

14.2

12.4

12.6

11.0

175

200

178

157

174627-174678

10 / 7.5

18.1

15.8

16.1

14.0

175

200

208

190

174628

15 / 11

27

24

24

21

155

180

418

174629

20 / 15

35

31

31

27

155

180

493

174630

25 / 18.5

44

38

39

34

155

180

645

174991

30 / 22

52

45

46

40

155

180

709

174992

40 / 30

68

59

60

52

155

180

1020

174710

50 / 37.5

85

74

75

65

155

180

1275

174711

60 / 45

100

87

88

77

155

180

1530

600 VAC Models

Type

Power

[Hp/kW]

Mains

Output Current

SM2

Watts

Loss

SM4

Watts

Loss

Voltage

(1)

I

in

I

n

CLim

max

(2)

174631-174663

1 / 0.75

600 V Three-phase (3/PE)

(425 … 660 V)

2.0

1.7

200

37

31

174632-174664

2 / 1.5

3.2

2.7

200

51

43

174633-174665

3 / 2.2

4.4

3.9

200

68

57

174634-174666

5 / 4.0

6.8

6.1

200

101

67

174635-174667

7.5 / 5.5

10.2

9

200

148

116

174636-174668

10 / 7.5

12.4

11

200

172

152

174637

15 / 11

19.7

17

180

380

174638

20 / 15

25

22

180

463

174639

25 / 18.5

31

27

180

560

174993

30 / 22

36

32

180

640

174994

40 / 30

47

41

180

930

174712

50 / 37.5

59

52

180

1163

174713

60 / 45

71

62

180

1395

(1) Frequency Range: 48 Hz … 62 Hz

(2) Current Limit (CLim) is a percentage of the output current, I

n

. CLim

max

is the maximum setting for P171.

For 480VAC models, the CLim

max

value in the 480V column of the table is used when P107 is set to 1.

The CLim

max

value in the 400V column is used when P107 is set to 0.

STOP!

Drive Derating

The SM2 and SM4 Vector Series drive is designed to operate at the Nominal Output Current (I

n

)shown

in the Ratings tables for most standard applications and industrial environments. The drive output

current or operating temperature may need to be limited as described below:

• For installations above 1000m a.m.s.l., derate I

n

by 5% per 1000m, do not exceed 4000m a.m.s.l.

• Operation above 40°C, derate I

n

by 2.5% per °C, do not exceed 55°C.

• Carrier Frequency (P166):

- If P166=2 (8 kHz), derate I

n

to 92% of drive rating or do not exceed 33°C ambient

- If P166=3 (10 kHz), derate I

n

to 84% of drive rating or do not exceed 27°C ambient

For combinations of the above, please consult LEESON applications support for proper derating.