Micro Series

Quick Reference Guide

NOTE: Before installing and operating the MICRO SERIES
drive, please read and become familiar with the MICRO SERIES
Installation and Operation Manual.

Adjustable Speed AC Motor Control

2

OUTPUT

ACCEL

In the example above, the second fault is being viewed, which is
an OUTPUT fault that occurred while the drive was accelerating.

FAULT

NUMBER

FAULT

MESSAGE

DRIVE

STATUS

MICRO SERIES FAULT HISTORY

Parameter 70 — FAULT HISTORY stores the last eight faults that
tripped the drive. The FAULT HISTORY indicates the number of
the fault (number 1 is the most recent fault), the fault message,
and the status of the drive at the time of the fault. An example is
shown below:

FAULT

DESCRIPTION

OUTPUT

Output Transistor fault. Output current exceeded 200%.

May be ground fault or short circuit.

LO VOLTS

Low DC Bus Voltage fault. DC bus voltage dropped below 60%

May be low line voltage.

HI VOLTS

High DC Bus Voltage fault. DC Bus voltage exceeded 120%.

May be overhauling load .

HI TEMP

High Temperature fault. Heatsink or ambient temperature

too high.

OVERLOAD

Current Overload fault. Output current exceeded 100% for

too long. VFD may be undersized.

PWR TRAN

Power Transient fault.

PWR SAG

Power Sag fault: New control board installed. Perform

factory reset using Parameter 65.

LANGUAGE

Language EEPROM fault.

EXTERNAL

External fault: TB-130 activated (Parameter 50).

DB ERROR

Dynamic Brake fault. DB Resistors overloaded.

CONTROL

Control Board fault. New solfware installed. Perform factory

reset using Parameter 65.

INTERNAL

Internal fault

INTERN (#)

Internal fault.

MC3000 FAULT MESSAGES

PARAMETER

FACTORY

PARAMETER

FACTORY

NO.

NAME

DEFAULT

NO.

NAME

DAFAULT

0

LINE VOLTS

AUTO

1

SPEED #1

20.00 Hz

2

SPEED #2

20.00 Hz

3

SPEED #3

20.00 Hz

4

SPEED #4

20.00 Hz

5

SKIP #1

.00 Hz

6

SKIP #2

.00 Hz

7

BAND WID

1.00 Hz

8

ACCEL

30.0 SEC

9

DECEL

30.0 SEC

10

MIN FRQ

.50 Hz

11

MAX FRQ

60.00 Hz

12

DC BRAKE

.0 VDC

13

DC TIME

.0 SEC

14

DYN BRAKE

OFF

16

CURRENT

180%

17

MOTOR OL

100%

18

BASE

60.00 Hz

19

FX BOOST

(NOTE 1)

20

AC BOOST

.0%

21

SLIP COMP

.0%

22

TORQUE

CONSTANT

23

CARRIER

2.5 kHz

25

START

NORMAL

26

STOP

COAST

27

ROTATION

FORWARD

28

AUTO/MAN

BOTH

29

MANUAL

KEYPAD

30

CONTROL

LOCAL

31

UNITS

HERTZ

32

HZ MULT

1

33

UNITS DP

XXXX

34

LOAD MLT

100%

35

CONTRAST

HIGH

39

TB5 MIN

.00 Hz

40

TB5 MAX

60.00 Hz

42

TB10A OUT

NONE

43

@TB10A

60.00 Hz

44

TB10B OUT

NONE

45

@TB10B

125%

47

TB13A

NONE

48

TB13B

NONE

49

TB13C

NONE

50

TB13D

FAULT

52

TB14 OUT

NONE

53

TB15 OUT

NONE

54

RELAY

NONE

58

ADDRESS

30

61

PASSWORD

0019

63

SOFTWARE

(NOTE 2)

64

MONITOR

ON

65

PROGRAM

RESET 60

66

HISTORY

MAINTAIN

70

FAULT HIST.

(NOTE 2)

NOTE 1: REFER TO THE MICRO SERIES MANUAL.

NOTE 2: THESE PARAMETERS ARE VIEW-ONLY.

MICRO SERIES PARAMETERS

Micro Series

Intelligent Drive

Digital

LEESON SPEEDMASTER

BULLETIN #2452 3/98