LEESON SM-Plus Series Remote Keypad Kit User Manual

LEESON Software

Advertising
background image

3.

MOUNTING THE REMOTE KEYPAD

The diagram below illustrates how to mount the remote keypad to a panel. Use
the template in Section 2 to mark the location of the mounting holes on the
panel.

PANEL

REMOTE

KEYPAD

GASKET

MOUNTING

SCREWS

2.

SM-PLUS REMOTE KEYPAD TEMPLATE

Hold this page against the panel where the remote keypad is to be mounted, and
use a center punch to mark the location of the three holes. The dotted line is the
outline of the remote keypad.

4.

WIRING CONNECTIONS

NOTE 1: The supplied cable can be used for distances up to 8 feet in low-noise
environments. For distances up to 100 feet, or in high-noise environments, use
Belden 9842, Carol C4842, or equivalent (24 gage minimum) wire only.

174191.00

- SM-PLUS SERIES

REMOTE KEYPAD

INSTRUCTIONS

The SM-Plus Series Remote Keypad option allows the SM-Plus Series
drive to be programmed and controlled from up to one hundred feet away.
When properly mounted, the remote keypad is rated NEMA 4X.

In addition to the functions available on the front of the SM-Plus drive,
the remote keypad has Start/Stop and Forward/Reverse functions.

NOTE: The Remote Keypad option will only work with SM-Plus drives that
have parameter version “309” or “312”. It will not work with SM-Plus
drives that have the High Frequency or PI Setpoint Control options. The
parameter version appears momentarily on the drive display when it is
powered up, and also appears on a small label on the drive’s heatsink.

1.

PARTS LIST

The SM-Plus Remote Keypad kit includes the following parts:

(1)

Remote Keypad

(1)

Gasket

(2)

Self-tapping Mounting Screws

(1)

Instruction Sheet

(1)

Eight foot cable

NOTE: The supplied cable can only be used for distances up to 8 feet in low-
noise environments. For distances up to 100 feet, or in high-noise environments,
use Belden 9842, Carol C4842, or equivalent (24 gage minimum) wire only.

WARNING!

If OEM mode is selected (using Parameter 48), and if the OEM Default setting
for Parameter 14 and/or 15 is “01”, the remote keypad will be disabled, and the

STOP

key WILL NOT work. Refer to the SM-Plus Installation and Operation

Manual for information on OEM Default settings.

WARNING!

Improper wiring may result in damage to the Remote Keypad. Keep the
remote keypad cable away from power wiring.

The Belden and Carol cables specified consist of two twisted pairs. Make
sure one twisted pair is used for power and the other is used for serial
communications. Do not mix connections between twisted pairs.

NOTE 2: TB-11 can supply up to 50
mA of power, and the remote keypad
requires 40 mA. To drive auxiliary relays
using the open-collector outputs, an
external power supply is required.

REMOTE KEYPAD

(BACK VIEW)

JUMPER

(See NOTE 2

in Section 5)

TXA

TXB

11

2

UP

TXA TXB

1

11

2

2

Cable included with kit
does not have a shield

SM-PLUS TERMINAL STRIP

Max Depth = 0.72”

1/8” hole

1/8” hole

1.57”

1.32”

1.38” to 1.5”

hole

3.38”

2.19”

UP

LEESON Electric

LEESON Electric

LEESON Electric

LEESON Electric