User Guide Silcon DP300E Series 480V 400-500kVA

7OA0004 US rev. 02

Alarms

Possible alarm

Description

Action

39. System is locked in oper.

mode

40 RAM1 memory write error
41. Memory write error
42. Communication to VQ

bypass lost

43. Communication to VQ

output lost

44. Communication to DMU

lost

45. Communication to control-

ler lost

46. Communication to parallel

IF lost

47. External shutdown

accepted

48. DC capacitor charge error

49. Communication to VQ

mains lost

50. Bypass sync error

UPS has attempted 10 times
within 1 min. to switch from
bypass to battery operation
or “High DC warning” has
appeared 10-20 times within
1 min.
Fault in UPS
Fault in UPS
Fault in UPS

Fault in UPS

Fault in UPS

Fault in UPS. Display will
show invalid data for UPS
Fault in UPS

Remote signal for switching
off the UPS accepted – UPS
switches off itself
Fault in DC charge circuit

Fault in UPS

The UPS cannot synchronize
to the bypass utility

If the system is locked in
bypass operation and the
alarm “Inverter voltage
error” exists in the alarm
stack do not try to unlock
the operations mode lock
but - call for assistance!

Call for assistance
Call for assistance
Call for assistance

Call for assistance

Call for assistance

Call for assistance

Call for assistance

Do NOT close
external MCCB due to
preventing damage of
UPS system.
Call for assistance

Call for assistance

Check if phase rota-
tion of bypass voltage
is correct - if OK, call
for assistance

NOTE:
Utility = Mains