System Sensor 8251F FAAST User Manual

Page 9

Advertising
background image

SS-600-000 9 I56-3904-001

FIGURE 14. BOTTOM VIEW OF UNIT

Wiring
Access

Plugs

Sampled

Air Inlet

Sampled

Air Outlet

Network

Connection

ASP-03

WEB SERVER
The FAAST system contains an integrated Web server which is used to ob-
serve detector configuration and may be used to remotely monitor the unit.

The Web server features include:

• Intuitive interface for remote monitoring of faults, relays, particulate

level, air flow, and power supply

• Facility location and contact information

• Configuration settings display
• Event log viewer

E-MAIL NOTIFICATION
The FAAST system has the ability to send e-mail notifications to an individual
or organization. Up to 6 different email addresses may be stored for notifica-
tion. Each email address can be configured to be notified of a specific alarm
level, fault level or isolate condition through the PipeIQ software. E-mails from
the device indicate a device’s ID, location and alarm or fault type. A com-
prehensive networking guide may be downloaded at systemsensor.com/faast.
CANNED SMOKE TESTING
All FAAST systems must be tested after installation and periodically thereafter.
Testing methods must statisfy the authority having jurisdiction. Systems of-
fer maximum performance when tested and maintained in compliance with
NFPA 72 and/or CAN/ULC S536 depending upon your national regulations..
UL Tested and approved aerosol smoke products are listed in Table 6.

MAINTENANCE
The only periodic maintenance required is to replace the filter assembly when
the filter light is illuminated. Perform the following procedure to replace the
filter assembly.

1. Remove power from the system.
2. Open the door on the right side of the device that covers the LED system

indicators.

3. Remove the plastic name card over the LEDs.
4. Remove the two screws holding the filter assembly into the device.
5. Remove the filter assembly and replace it with a new assembly.
6. Torque the two philips head screws to 6in-lb (0.7 N-M) or ¼ turn past

“lightly snug.” PLEASE DO NOT OVERTIGHTEN.

7. Replace the plastic name card over the LEDs.
8. Close the door and return power to the system.

Other system checks may need to be performed in accordance with local or
national codes and regulations.