Horns silenced over two wire circuit – System Sensor MDL and MDLW User Manual

Page 2

Advertising
background image

Figure 1: Single MDL Using Sync Error (for panels
with the capability to check for sync error)
NOTE:
If zone 1 output of module is connected to strobes,
chime/strobes or horn/strobes, zone 1 input supply power
must be continuous for proper operation.

TEMP. JUMPER OFF

NAC2

NAC1

FACP

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

HORN

CONTROL

ZONE 1

OUT

ZONE 1

IN

ZONE 2

IN

SLAVE

IN

ZONE 2

OUT

SYNC

ERROR

SLAVE

OUT

SEPARATE

MONITORING

INPUT

EOL

A0262-00

Figure 2:
NOTE:
If zone 1 output of module is connected to strobes,
chime/strobes or horn/strobes, zone 1 input supply power
must be continuous for proper operation.

TO NEXT

SPECTRALERT

DEVICE OR

EOL

NAC3

NAC2

MASTER MODULE

SLAVE MODULE

NAC1

TO NEXT

SPECTRALERT

DEVICE OR

EOL

All SpectrAlert horns,

horn/strobes, and strobes

will operate in sync.

NAC2

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

HORNS SILENCED OVER TWO WIRE CIRCUIT

MASTER MODULE HORN CONTROL CONNECTS

TO INTERRUPTABLE POWER SOURCE

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

HORN

CONTROL

ZONE 1

OUT

ZONE 1

IN

ZONE 2

IN

SLAVE

IN

ZONE 2

OUT

SYNC

ERROR

SLAVE

OUT

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

HORN

CONTROL

TEMP JUMPER OFF

ZONE 1

OUT

ZONE 1

IN

ZONE 2

IN

SLAVE

IN

ZONE 2

OUT

SYNC

ERROR

SLAVE

OUT

TEMP JUMPER OFF

FACP #1

FACP #2

TO NEXT

SPECTRALERT

DEVICE OR

EOL

TO NEXT

SPECTRALERT

DEVICE OR

EOL

NAC1

(+)

(–)

EOL

A0182-00

D900-14-00

2

I56-0983-015R

Synchronize SpectrAlert Horns, Chimes and Strobes
• Each module can power two 3-amp circuits wired in

class B or one 3-amp circuit powered as Class A.

• Each module will synchronize 2 zones.
• Additional modules can be added and may be syn-

chronized to all other modules by interconnecting the
“slave” input and output terminals between modules.

CAUTION

Horn control wiring must be contained within common en-
closure of module.

CAUTION

Slave Out – Slave In wiring must be contained within either
the common enclosure of modules or enclosures within 20
feet of each other with wiring inside conduit.

CAUTION

If Zone 1 input is not powered or fails during alarm, the
notification devices attached to the Zone 2 output will not
be powered.

Controlling Sounder On/Off Over 2-Wires Using Mod-
ule Horn Control
• Connect the current source to the horn or chime control

input. If a zone output is used for the source, you must
use an EOL on the horn control input terminal.

• When multiple modules are used, the horn or chime

control circuits can be wired in parallel. If wired in par-
allel and a zone output is used from panel, use an EOL
on the last module for supervision.

CAUTION

Horn/chime control wiring must be contained within com-
mon enclosure of module.

CAUTION

Slave Out – Slave In wiring must be contained within either
the common enclosure of modules or enclosures within 20
feet of each other with wiring inside conduit.

CAUTION

If Zone 1 input is not powered or fails during alarm, the
notification devices attached to the Zone 2 output will not
be powered.

Special Considerations
A latching relay contact is provided in case the synchro-
nizing signal to the notification devices is interrupted. The
output can be wired so that a trouble signal will be annun-
ciated at the panel. If the synchronization pulse fails in the
MDL module, the strobes will shut off.