System Sensor MHR and MHW User Manual

Page 2

Advertising
background image

D690-07-00

2 I56-2958-001R

©2012 System Sensor

SOUNDER SELECTION
Sounder setting selection is accomplished by using the rotary switch on the
back (see Figure 3). The sound measurements for the various settings are
shown in Table 1A. The current draw for the various settings is shown in
Table 1B.

TAbLE 1A.
SOUNDER OUTpUT (dbA) REvERbERANT

SWITCH

SETTING

PATTERN

OUTPUT

LEVEL

8

VDC

8

VFWR

12

VDC

12

VFWR

16-33

VDC

16-33

VFWR

1

TEMPORAL HIGH

68

67

71

70

78

76

2

TEMPORAL

LOW

66

65

69

68

76

75

3

NON-

TEMPORAL

HIGH

72

71

75

74

80

79

4

NON-

TEMPORAL

LOW

70

69

73

72

78

77

TAbLE 1b.
SOUNDER CURRENT DRAW (mA RMS)

SWITCH

POSITION

SOUND

PATTERN

VOLUME

8-17.5 VOLTS

16-33 VOLTS

DC

FWR

DC

FWR

1

TEMPORAL

HIGH

12

10

17

15

2

TEMPORAL

LOW

10

9

14

13

3

NON-

TEMPORAL

HIGH

22

17

29

25

4

NON-

TEMPORAL

LOW

17

13

21

19

The horn will not work without power. The horn gets its power from the fire/security
panel monitoring the alarm system. If power is cut off for any reason, the horn will not
provide the desired audio or visual warning.
The horn may not be heard. The loudness of the horn meets (or exceeds) current
Underwriters Laboratories’ standards. However, the horn may not alert a sound sleeper or

one who has recently used drugs or has been drinking alcoholic beverages. The horn may
not be heard if it is placed on a different floor from the person in hazard or if placed too
far away to be heard over the ambient noise such as traffic, air conditioners, machinery
or music appliances that may prevent alert persons from hearing the alarm. The horn
may not be heard by persons who are hearing impaired.

THE LIMITATIONS Of HORNS

WARNING

THREE-yEAR LIMITED WARRANTy

System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for this product. No agent,
representative, dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation of this Warranty
shall be limited to the replacement of any part of the product which is found to be defec-
tive in materials or workmanship under normal use and service during the three year
period commencing with the date of manufacture. After phoning System Sensor’s toll
free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defec-
tive units postage prepaid to: System Sensor, Returns Department, RA #__________, 3825

Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and
suspected cause of failure. The Company shall not be obligated to replace units which
are found to be defective because of damage, unreasonable use, modifications, or altera-
tions occurring after the date of manufacture. In no case shall the Company be liable
for any consequential or incidental damages for breach of this or any other Warranty,
expressed or implied whatsoever, even if the loss or damage is caused by the Company’s
negligence or fault. Some states do not allow the exclusion or limitation of incidental or
consequential damages, so the above limitation or exclusion may not apply to you. This
Warranty gives you specific legal rights, and you may also have other rights which vary
from state to state.

fCC STATEMENT

SpectrAlert Strobes and Horn/Strobes have been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when the equip-
ment is operated in a commercial environment. This equipment generates, uses, and

can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause harmful interference in which
case the user will be required to correct the interference at his own expense.

Please refer to insert for the Limitations of Fire Alarm Systems

MOUNTING
1. The MH Mini-Horn is intended for mounting to a standard 2½˝ deep

single gang box or a standard 4 × 4 box, with single gang mud ring,
which allows sufficient clearance for conduit entrance.

2. The MH Mini-Horn is compatible with DC line supervision. The horn is

polarized and has terminals marked with polarity. Apply positive supply
voltage to the (+) terminal and negative to the (–) terminal. (See Figure 3)

3. Mount the horn to the electrical outlet box using the two mounting

screws supplied.

NOTE: SHOWN WITH CONTROL PANEL IN ALARM. PANEL POLARITY

REVERSED IN SUPERVISORY CONDITION.

TO EOL

OR

NEXT

DEVICE

FROM

CONTROL

PANEL OR

PREVIOUS

DEVICE

fIGURE 3.

A0358-00