Shorting spring – System Sensor Dual Strobe Expander Plates User Manual

Page 2

Advertising
background image

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

Input from

FACP or Prior

Fire Strobe

Input from Power

Supply for Alert Strobe

or Prior Alert Strobe

Output to Next

Fire Strobe or EoL

Output to Next

Alert Strobe or EoL

SS-120-005

2 I56-3829-001R

moUnTinG The Sep-SpSW Speaker STrobe expander pLaTe
1. Attach the speaker strobe expander plate to the junction box as shown in

Figure 5. The speaker strobe expander plate is compatible with a 4˝ x 4˝
x 2

1

/

8

˝ junction box. If using a back box skirt, attach the speaker strobe

expander plate to the back box skirt and then attach the entire assembly
to the junction box (see figure 6).

2. Connect the field wiring to the terminals, as shown in Figure 1.
3. If the speaker strobe device is not to be installed at this point, use the

paint cover to prevent contamination of the speaker strobe expander
plate.

4. To attach the speaker strobe device to the speaker strobe expander plate,

remove the paint cover, then hook the tabs on the product housing into
the grooves on the strobe plate.

5. Swing the speaker strobe device into position to engage the pins on the

device with the terminals on the speaker strobe expander plate. Make
sure that the tabs on the back of the device housing fully engage with the
expander plate.

6. Secure the speaker strobe device by tightening the single mounting

screw in the front of the speaker strobe housing. For tamper resistance,
the standard captive mounting screw may be replaced with the enclosed
Torx screw.

TabLe 1. STrobe CUrrenT draW ( ) For Sep-SW, Sep-SpSW:

ma

A0447-00

A0448-00

SHORTING SPRING

FiGUre 3. WirinG The Sep-SW: STrobe expander pLaTe,
STandard CandeLa, WhiTe:

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

Input from

Amplifier or

Prior Speaker

Input from

FACP or Prior

Fire Strobe

Output to Next

Speaker or EoL

Output to Next

Fire Strobe or EoL

(+)

(–)

(+)

(–)

Input from Power

Supply for Alert Strobe

or Prior Alert Strobe

Output to Next Alert

Strobe or EoL

A0446-00

Shorting Spring

FiGUre 2. ShorTinG SprinG on Sep-SpSW Speaker STrobe
expander pLaTe, STandard CandeLa,WhiTe:

FiGUre 4. ShorTinG SprinG on Sep-SW STrobe expander
pLaTe, STandard CandeLa, WhiTe:

A0445-00

FiGUre 1. WirinG Sep-SpSW Speaker STrobe expander pLaTe,
STandard CandeLa,WhiTe:

Candela

8–17.5 Volts

16–33 Volts

DC

FWR

DC

FWR

Standard Candela Range

15

123

128

66

71

15/75

142

148

77

81

30

NA

NA

94

96

75

NA

NA

158

153

95

NA

NA

181

176

110

NA

NA

202

195

115

NA

NA

210

205

NOTE: The total number of strobes on a single NAC must not exceed 40 for
24 volt applications or 12 for 12 volt applications. Loop resistance on a single
NAC should not exceed 120 ohms for 24 volt and 30 ohms for 12 volt systems.

NOTE: A shorting spring is provided between terminals 2 and 3 of the mount-
ing plate to enable wiring checks after the system has been wired, but prior
to installation of the final product. This spring will automatically disengage
when the product is installed, to enable supervision of the final system.

TabLe 2: CandeLa deraTinG For amber LenS STrobe

Cd Switch Setting

On-Axis Rating

(UL 1638)

Equivalent Cd Rating for

Wall profile (UL 1971)

15

15

12

15/75

15/75

15/75

30

30

24

75

75

60

95

95

75

110

110

85

115

115

90

NOTE: UL1971 is not applicable to mass notification devices, but these read-
ings were obtained using the measurement procedure specified under UL1971.

IMPORTANT: For more information on current draw, light output and sound
output data, reference Speaker Strobe installation manual I56-3935 and Strobe
only installation manual I56-2769.

NOTE: Shorting springs are provided between terminals 2 and 3 and terminals
5 and 6 of the mounting plate to enable wiring checks after the system has
been wired, but prior to installation of the final product. These springs will
automatically disengage when the product is installed, to enable supervision
of the final system.

Advertising