Watt setting – System Sensor PF24 Exitpoint User Manual

Page 2

Advertising
background image

D550-10-00

2

I56-2600-02R

The same number of devices using 12 AWG wire will
produce only a 2 volt drop. The same number of devices
using 18 AWG wire will produce an 8 volt drop. Consult
your panel manufacturer’s specifications, as well as the
sounder’s operating voltage to determine the acceptable
voltage drop.

NOTE: If class “A” wiring is installed the wire length may

be up to 4 times the single wire length in this cal-
culation.

Table 1: Current Draw Measurements and
Sound Output Guide

Speed Selection

Power

Setting

Maximum DC

Operating

Current

(mA RMS)

(16 to 33V)

Audibility

(dBA)
(16 to

33V)

Note 1

Audibility

(dBA)
(16 to

33V)

Note 2

Speed

Switch

Selection

FAST (exit)

10

4 Watt

225

85

78

FAST (exit)

10

2 Watt

114

82

76

FAST (exit)

10

1 Watt

75

79

73

FAST (exit)

10

1

/

2

Watt

62

76

69

FAST (exit)

10

1

/

4

Watt

49

73

66

MED1

9

4 Watt

221

85

77

MED1

9

2 Watt

112

82

74

MED1

9

1 Watt

74

79

71

MED1

9

1

/

2

Watt

61

76

68

MED1

9

1

/

4

Watt

48

73

65

MED2

8

4 Watt

203

85

78

MED2

8

2 Watt

103

82

75

MED2

8

1 Watt

68

79

73

MED2

8

1

/

2

Watt

56

76

69

MED2

8

1

/

4

Watt

44

73

66

SLOW

7

4 Watt

189

85

76

SLOW

7

2 Watt

96

82

73

SLOW

7

1 Watt

63

79

70

SLOW

7

1

/

2

Watt

52

76

67

SLOW

7

1

/

4

Watt

41

73

64

NOTE 1: Sound output measured in anechoic room at 10 feet.
NOTE 2: Sound output measured in a reverberant room at 10 feet.

Installation
Consult the Directional Sound Applications Guide for
information regarding the appropriate mounting locations
of directional sounders.

Switch Settings
Selections are made via DIP switches on the back of
the sounder. Switch positions 7-10 are used to select the
pulse pattern of the sounder. Switch 10 is used to mark
the perimeter exit locations (fastest pulse). The remaining
settings are used for egress routing to the perimeter exit.
The egress route would originate with the “slow” (switch
7) tone and follow “medium 2” (switch 8) to “medium 1”
(switch 9) and finally the exit point “fast” (switch 10). If

more than one switch is selected the sounder will default
to the fastest selected setting.

Switch positions 5 and 6 are used to select additional
tone pulses that can be inserted in between bursts of the
directional sound pulses. The additional tone pulse will
be inserted on every 6th directional sound pulse. These
switches should be used when the sounder will be placed
near a stairway to guide a building occupant up or down
the stairs. Switch setting 5 inserts a down sweep indicat-
ing the presence of a downward stairway. Switch setting 6
inserts an up sweep indicating the presence of an upward
stairway. If switch positions 5 and 6 are both set to “on”
this will insert a special tone for use near areas of refuge.
The area of refuge tone should be used if the directional
sounder is marking an area of refuge. This tone provides
a distinct signal indicating that the sounder is not mark-
ing an exit. If both switches are set to “off” the sounder
will default to no additional tones. In this case only the
directional sound pulses will be heard. See Table 2 for tone
selection options.

Table 2: Additional Tone Selection Guide

Switch

Position 5

Setting

Switch

Position 6

Setting

Sound Output

on

on

Refuge

on

off

DOWN Stairs

off

on

UP Stairs

off

off

no tones

Switch setting 4 enables a directional sound device to
become disabled when used in conjunction with devices
with dry contacts such as heat sensors or control modules.
The sounder has a set of input terminals that can be con-
figured for an “active open” or “active closed” state. When
the switch is in the “on” position, the sounder is “on”
when the disable connection is closed. When the switch is
in the “off” position, the sounder is “on” when the disable
connection is open. See Table 3 for operation modes.

Table 3: Enable/Disable Function Logic Table

Switch

Position 4

Setting

Terminals 3

& 4

Sound

Output

on

open

disabled

on

closed

enabled

off

open

enabled

off

closed

disabled

There are five different power settings for the sound output
pressure. Switch settings 1, 2, and 3 set the power setting
for the sounder. Switch 1 selects the 2 watt setting, switch 2
selects the 1 watt setting, switch 3 selects the

1

/

2

watt setting.

If all three switches are “off” this selects the 4 watt setting and
if all three switches are “on” this selects the

1

/

4

watt setting.

Advertising