Figure 2, Figure 3 – System Sensor PF24V Exitpoint User Manual

Page 3

Advertising
background image

D690-06-00

3 I56-2961-001R

FIGURE 1.

TWO WIRE SYSTEM

ANY MIX OF MODELS

OPTIONAL DISABLE CONTACT

NOTE: SWITCH POSITION 4 SETS

THIS INPUT TO EITHER

ACTIVE OPEN OR ACTIVE CLOSED.

HORN

(+)

(–)

(+)

(–)

E

O

L

(+)

(–)

(+)

(–)

(+)

(–)

HORN/STROBE

DIRECTIONAL

SOUNDER

STROBE ONLY

A0338-00

FIGURE 2.

FOUR WIRE SYSTEM:

ANY MIX OF HORNS

AND SOUNDERS OR

HORN/STROBES

HORN/STROBE

(+)

(–)

(+)

(–)

E

O

L

(+)

(–)

(+)

(–)

HORN

DIRECTIONAL

SOUNDER

FOUR WIRE SYSTEM:

ANY MIX OF STROBES

AND HORN/STROBES

STROBE

POWER

SUPPLY

SOUNDER

POWER

SUPPLY

(+)

(–)

(+)

(–)

E

O

L

(+)

(–)

STROBE

A0344-00

FIGURE 3.

ROTARY SWITCH

USED FOR

LANGUAGE

SELECTION

DIP SWITCHES

USED FOR SPEED

SETTINGS, POWER

SELECTION,

ADDITIONAL TONES,

AND DISABLE

FUNCTION

NOTE: DO NOT loop electrical wiring under terminal screws. Wires connect-
ing the device to the control panel must be broken at the device terminal con-
nection in order to maintain electrical supervision. See Figure 4.

FIGURE 4.

BREAK WIRE AS SHOWN FOR

SUPERVISION OF CONNECTION.

DO NOT ALLOW STRIPPED WIRE

LEADS TO EXTEND BEYOND SWITCH

HOUSING. DO NOT LOOP WIRES.

A0337-00

The sounder has a set of input terminals to provide additional control of the
sound output of the directional sounder. These terminals can be connected to
the dry relay contacts of control devices such as heat sensors or control mod-
ules. When the input is active it will disable the sound output of the Sounder.
Connect the disable function as shown in Figure 5. Refer to Table 3 for func-
tion switch settings.
FIGURE 5.

– VDC

TO NEXT DEVICE

OR EOL

OPTIONAL DISABLE CONTACT

+ VDC

MECHANICAL
Two screws are included for attaching the sounder to the electrical junction
box.
NOTE: If surface mounting is required, an extension ring will be necessary to
give proper depth for mounting the sounder. The minimum depth required,
in the backbox/extension ring combination, is 2¼˝. Any combination of 4˝ ×
4˝ backbox and 4˝ × 4˝ extension ring that gives an interior depth of at least
2¼˝ may be used.

MOUNTING
See Figure 6. The sounder can be flush mounted on a 4˝ Ч 4˝ Ч 2¼˝ back
box, as follows:

A. Use the two 8-32 × 1¾˝ screws (provided) to attach the Sounder to

the back box.

B. Plug the remaining two holes that will not be used for attachment

with the plugs provided.

FIGURE 6.

4" x 4" x 2-1/4"
BACKBOX

PF24V

8-32

SCREWS

FILL

PLUGS

Skirt, BBS-SP201W

A0359-00

C0928-00

A0929-00

4" x 4" x 2-1/4"
BACKBOX

PF24V

8-32

SCREWS

FILL

PLUGS

A0176-05

Advertising