System Sensor RP12_24ADA Series Retrofit Strobes User Manual

Installation and maintenance instructions

Advertising
background image

D900-09-00

1

I56-757-02

RP12/24ADA Series Retrofit

Strobes for Fire Protective

Signaling Systems

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

NOTICE: This manual should be left with the owner/user
of this equipment.

General Description
The National Fire Protection Association has published
standards and recommended practices for the installation
and use of the listed appliances. It is recommended that the
installer be familiar with these requirements, with local
codes, and any special requirements of the local fire au-
thority having jurisdiction.

The RP12/24ADA series retroplates are ADA compliant (75
and 110 cd models) signaling devices and designed for use
in existing or new installations. They are a low-cost alterna-
tive to replacing a sounder with a new sounder/strobe.
This signaling strobe is intended to be connected to the
alarm indicating circuit of a UL-listed fire alarm control

Figure 1. Vertical and horizontal light distribution:

LIGHT

–45˚

45˚

90˚

–90˚

Percent of
Degrees Rating
0

100

5 - 25 90

30 - 45 75
50 55
55 45
60 40
65 35
70 35
75 30
80 30
85 25
90 25

Table 1. RP12/24ADA Series electrical ratings:

Model

Supply

Voltage

Range

Operating Current from Regulated Supply

Operating Current from Full-Wave Rectified Unfiltered

Supply

Average

Operatin

Current

Peak

Current

(mA)

20/30V

Peak

Current

(mA)

10.5V/17V

Inrush

Current

(mA in

access of

Peak)

Average

Operating

Current

(mArms)

Peak Current

(mA)

20Vrms/30Vrms

Peak Current

(mA)

10.5Vrms/17Vrms

Inrush Current

(Amps in

excess of Peak)

RP24110ADA
RP24110ADAW

20-30V

210

470/500

-

0

245

400/500

-

0.08

RP2475ADA
RP2475ADAW

20-30V

170

385/400

-

0

200

320/370

-

0.04

RP2415ADA
RP2415ADAW

20-30V

75

160/180

-

0

90

275/290

-

0.02

RP1215ADA
RP1215ADAW

10.5-17V

170

-

360/380

0

200

-

330/380

0.02

RP241575ADA
RP241575ADAW

20-30V

93

210/220

--

0

120

275/290

--

1

RP121575ADA
RP121575ADAW

10.5-17V

225

--

510/560

0

270

--

500/530

0.02

NOTE: In-rush current du-

ration is less than
20 microseconds
(0.00002 seconds).

panel. It is compatible with DC line supervision. Models
RP2415ADA, RP2475ADA, RP24110ADA, and
RP241575ADA require 24 volt panels. Models RP1215ADA
and RP121575ADA require 12 volt panels. Panels may have
full-wave rectified, unfiltered power supplies. The strobes
produce one flash per second (nominal) with continuous
nominal voltage applied.

The rated light output of the RP2415ADA, RP1215ADA,
RP241575ADA, and RP121575ADA is 15 cd (see Figure 1).

The rated light output of the RP2475ADA is 75 cd (please
see Figure 1).

The rated light output of the RP24110ADA is 110 cd (please
see Figure 1).

NOTE: The light output at 0

°

viewing angle for RP12/

241575ADA models is 75 cd (see Figure 1).