Figure 1a: current draw measurements (rms), Candela equivalent at –40°c and below – System Sensor S1224MCK, P1224MCK and H12_24K User Manual

Page 2

Advertising
background image

D900-37-00

2

I56-2257-005R

Typical wire size resistance:
18 AWG solid:

Approximately 8 ohms/1,000 ft.

16 AWG solid:

Approximately 5 ohms/1,000 ft.

14 AWG solid:

Approximately 3 ohms/1,000 ft.

12 AWG solid:

Approximately 2 ohms/1,000 ft.

Example: Assume you have 10 devices on a zone and each re-
quires 50 mA average and 2000 Ft. of 14 AWG wiring (total
length=outgoing +return). The voltage at the end of the loop is
0.050 amps per device x 10 devices x 3 ohms/1,000 ft. x 2000 ft
=3 volts drop.
NOTE: If class “A” wiring is installed, the wire length may be up
to 4 times the single wire length in this calculation.
The same number of devices using 12 AWG wire will produce only
2 volts drop. The same devices using 18 AWG wire will produce
8 volts drop. Consult your panel manufacturer’s specifications, as
well as SpectrAlert’s operating voltage range to determine accept-
able voltage drop.

Figure 1A: Current Draw Measurements (RMS)

NOTE: All ‘S’ and ‘P’ models were only tested at the 8-17.5 and
16-33 Volt-FWR/DC limits. This does not include the 80% low-
end or 110% high-end voltage limits.

Strobe Current Draw

Candela

Setting

FWR

Operating

Current

Strobe

DC

Operating

Current

Strobe

12V

24V

12V 24V

15

112

64

127

59

15/75

135

74

127

69

30

93

90

75

158

160

110

208

209

NOTE: 12 VDC 2-wire horn/strobe current is shown in Figure 1D.
24VDC 2-wire horn/strobe current draw is shown in Figure 1E.
Horn/Strobe current draw can be calculated by adding the strobe
current draw (Figure 1A) for chosen candela setting to the horn
current draw (Figure 1C) for chosen setting.

Figure 1B: Horn Sound Measurements (dBA):

Selectable Horn Tones

8-17.5V

16-33V

Temporal

Low
Volume

Electromechanical

67

75

3000 Hz Interrupted

68

75

High
Volume

Electromechanical

71

80

3000 Hz Interrupted

72

81

Non-
Temporal

Low
Volume

Electromechanical

71

79

3000 Hz Interrupted

72

79

High
Volume

Electromechanical

76

84

3000 Hz Interrupted

77

86

Figure 1C: Horn Current Draw Measurements (RMS):

Selectable Horn Tones

DC

FWR

12V

24V

12V

24V

Temporal

Low
Volume

Electromechanical

15

23

13

23

3000 Hz Interrupted

15

33

13

23

High
Volume

Electromechanical

36

53

20

44

3000 Hz Interrupted

43

57

21

40

Non-
Temporal

Low
Volume

Electromechanical

16

37

19

29

3000 Hz Interrupted

16

32

18

33

High
Volume

Electromechanical

38

49

46

49

3000 Hz Interrupted

44

56

42

58

NOTE: Regulated 12 VDC, max operating current 44.4 mA

Regulated 24 VDC, max operating current 57.0 mA

12 V FWR, max operating current 45.7 mA

24 V FWR, max operating current 57.5 mA

Figure 1D: 12VDC Horn/Strobe Current Draw

Measurements (mA RMS)

Temporal

Low Volume

High Volume

Candela

Setting

Electromechanical

3000 Hz

Electromechanical

3000 Hz

15

111

111

112

112

15/75

127

127

126

129

Non-Temporal

15

113

112

114

115

15/75

128

128

130

134

Figure 1E: 24VDC Horn/Strobe Current Draw

Measurements (mA RMS)

Temporal

Low Volume

High Volume

Candela

Setting

Electromechanical

3000 Hz

Electromechanical

3000 Hz

15

71

70

73

75

15/75

86

85

87

88

30

99

98

100

100

75

166

166

167

170

110

209

209

210

213

Non-Temporal

15

74

74

79

82

15/75

86

88

93

96

30

101

101

107

110

75

167

167

173

176

110

213

213

218

222

Candela equivalent at –40°C and below:

15cd

3cd

15/75cd

20cd

30cd

9cd

75cd

27cd

110cd

46cd

Advertising