Figure 3, Table 2. strobe characteristics, Table 3 – System Sensor SP100ADA Series Dual-transformer Speaker_Strobes User Manual

Page 3

Advertising
background image

D400-55-00

3

I56-691-03

LIGHT

–45˚

45˚

90˚

–90˚

Figure 3:

Degrees

% of Rating

0

100

5 - 25

90

30 - 45

75

50

55

55

45

60

40

65

35

70

35

75

30

80

30

85

25

90

25

Table 2. Strobe characteristics:

Model

Supply

Voltage

Range

Operating Current from Regulated

Supply

Operating Current from Full-Wave Rectified

Unfiltered Supply

Average

Operating

Current

Peak

Current

(mA)

20/30V

Inrush

Current

(mA in

access of

Peak)

Average

Operating

Current

(mArms)

Peak Current

(mA)

20Vrms/30Vrms

Inrush Current

(Amps in excess

of Peak)

SP1R24110ADA
SP1W24110ADA

20-30V

210

470/500

0

245

400/500

0.08

SP1R2475ADA
SP1W2475ADA

20-30V

170

385/400

0

200

320/370

0.04

SP1R2415ADA
SP1W2415ADAB

20-30V

75

160/180

0

90

275/290

0.02

SP1R241575ADA
SP1W241575ADA

20-30V

93

210/220

0

120

275/290

1.0

Note: Inrush current lasts on the order of microseconds

Table 3:

SP100W24MC

LO = 1.5 cd UL 1638 Strobe
M = 15 cd UL 1638 Strobe

24 = 24 VDC Strobe

SP100W = Round Grille, White Speaker
SP101W = Square Grille, White Speaker
SP101R = Square Grille, Red Speaker

C = Ceiling mount

SP1R2415ADA

15 = 15 cd, UL 1971 Strobe
1575 = 15 cd UL 1971 Strobe
75 = 75 cd, UL 1971 Strobe
110 = 110 cd, UL 1971 Strobe

24 = 24 VDC Strobe

SP1R = Square Grille, Red Speaker
SP1W = Square Grille, White Speaker
V4R = V400 Square, Red Speaker

Strobe Light Ratings
The signaling strobe is rated for 0

°

to 49

°

C and is not suit-

able for outdoor use.

The rated light output of the SP1

*

2415ADA and

SP1*241575ADA is 15 cd (See Figure 3).

The rated light output of the SP1

*

2475ADA is 75 cd (See

Figure 3).

The rated light output of the SP1

*

24110ADA is 110 cd (See

Figure 3).

NOTE: The light output at 0

°

viewing angle for

SP1*241575ADA is 75 cd (See Figure 3).

R = Red
W = White

Advertising