System Sensor SP2C Series Ceiling Mount Speaker_Strobes User Manual

Page 2

Advertising
background image

Example: Assume you have 10 devices on a zone and each
requires 50 mA average and 2000 Ft. of 14 AWG wiring
(total length=outgoing+return). The voltage at the end
of the loop is 0.050 amps per device×10 devices×3 ohms
1,000 ft.×2000 ft =3 volts drop.

The same number of devices using 12 AWG wire will produce only
2 volts drop. The same devices using 18 AWG wire will produce
8 volts drop. Consult your panel manufacturer’s specifications, as
well as SpectrAlert’s operating voltage range to determine accept-
able voltage drop.

Installation
All wiring must be installed in compliance with the National
Electrical Code (NEC) and applicable local codes as well as
special requirements of the authority having jurisdiction, using
the proper wire size. This also includes all applicable NFPA
Standards, ANSI/UL 1480, UL 1971 and NEC 760.

NOTE: Supply power for strobe must be continuous for

proper operation.

Figure 1. Electrical connections:

Figure 2. Voltage and Power Selection:

25.0V

70.7V

2W

1W

1/2W

1/4W

25.0V

70.7V

2W

1W

1/2W

1/4W

CORRECT

SW1

SW
1

INCORRECT

TO NEXT

STROBE OR EOL

INPUT FROM

POWER SUPPLY

INPUT FROM

AMPLIFIER

TO NEXT

SPEAKER OR EOL

STROBE

SPEAKER

Table 1. Sound levels for each transformer

power tap:

D690-02-00

2

I56-1455-009R

Electrical
1. Connect the speaker/strobe as shown in Figure 1. Keep in mind

that even though the speaker and strobe are a single mechani-
cal unit, they are electrically independent and require separate
power sources.

NOTE: Do NOT loop electrical wiring under terminal screws.

Wires connecting the device to the control panel must
be broken at the device terminal connection in order to
maintain electrical supervision.

Table 2: Current draw of strobes

NOTE: All strobes were only tested at the 16-33 Volt-FWR/

DC limits. This does not include the 80% low end
or 110% high end voltage limits.

Model No.

FWR Max. Operating

Current – Strobe

(mA RMS)

DC Max. Operatng

Current – Strobe

(mA RMS)

SP2C2415

68

64

SP2C241575

77

78

SP2C2430

107

113

SP2C2475

197

205

SP2C2495

239

274

SP2C24115

298

325

SP2C24177

399

489

A0101-00

A0102-00

INPUT

VOLTS

2 W

1 W

1

/

2

W

1

/

4

W

25.0 &

70.7

84

81

78

75

UL

Reverberant

(dBA @ 10 ft.)

Advertising