System Sensor V4R24ADA Series Speaker_Strobes User Manual

System Sensor Equipment

Advertising
background image

D900-02-00

1

I56-655-03

V4R24ADA Series Speaker/Strobes

for Fire Protective Signaling Systems

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

General
The National Fire Protection Association has published
standards and recommended practices for the installation
and use of the appliances described in these instructions. It
is recommended that the installer become familiar with
these standards and practices, local codes, and any special
requirements of the authority having jurisdiction.

The speakers can operate at any one of four input power
levels at either of two input voltages. The system voltage
and sound power levels are selected at the time of installa-
tion, but can be changed, if necessary.

Strobe

Specifications
Speaker
Frequency Range:

400 Hz to 4000Hz

Supervision:

Capacitive input for supervisory DC voltage

Mounting:

Standard 4" X 4" electrical box
Surface mount directly to box
Semiflush mount, using model MP-SF or MP-SFB

Model

Supply

Voltage

Range

Operating Current from

Regulated Supply

Operating Current from Full-Wave

Rectified Unfiltered Supply

Average

Operating

Current

Average

Operating

Current

(mArms)

Peak

Current

(mA)

20Vrms/

30Vrms

Peak

Current

(mA)

20/30V

Inrush

Current

(mA in
access

of Peak)

Inrush

Current

(Amps in

excess

of Peak)

V4R24110ADA

V4R2475ADA

V4R2415ADA

V4R241575ADA

20-30V

210

470/500

0

245

400/500

0.08

20-30V

170

385/400

0

200

320/370

0.04

20-30V

75

160/180

0

90

275/290

0.02

20-30V

93

210/220

0

120

275/290

1.0

NOTE: Inrush current duration is less than 20 microseconds (.00002 seconds).

Input

Voltage

(Vrms)

Power

Tap

(Watts)

Minimum Output (dBA)

UL

Reverberant

Anechoic

@ 10 ft.

25 or 70.7

1/4

75

78

25 or 70.7

1/2

78

81

25 or 70.7

1

81

84

25 or 70.7

2

84

87

The speaker is also equipped with a capacitive input to al-
low for DC supervision.

An attached 24 VDC strobe at 110, 75, 15, or 15/75 candela
(cd) is also included with the speaker. Although they are
assembled into a unit, the strobe and speaker are electri-
cally independent and require separate power sources.

Strobes can be powered by means of a full-wave rectified
unfiltered supply.

Advertising