System Sensor 6424 Projected Beam Type User Manual

6424 projected beam type smoke detector

Advertising
background image

D400-18-00

1

I56-494-13R

PRINTED IN MEXICO

6424 Projected Beam Type
Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Specifications
General
Range:

30 to 330 Feet (9.1 to 100.6 m)

Sensitivity:

30% ±5% Total Obscuration, or

55% ±5% Total Obscuration

Spacing:

30 to 60 Feet (9.1 to 18.3 m)

Response Time:

Alarm:

15 Seconds Max.

Trouble:

15 Seconds Max.

Trouble Condition:

95% or More Obscuration

Improper Initial Alignment

Self-compensation limit reached (service needed)

Test/Reset Features:

Obscuration Filters (ALARM/NO ALARM)

Local Alarm Reset Switch

Remote Test and Reset Switch Capability

(compatible with RTS451 Test Station with Magnet)

Indicators:

Alarm:

Remote Output, Local LED (red)

Trouble:

Remote Output, Local LED (yellow)

Normal Operation: Local LED (flashing green)

Alignment Aid:

LED Bar Graph (4 red LEDs)

Relays:

Alarm; Trouble

Environmental
Temperature:

–22°F to 131°F (–30°C to 55°C)

Humidity:

10% to 93% RH Noncondensing

Mechanical
Weight:

Receiver:

1.5 lbs (680 g)

Transmitter: 1.3 lbs (590 g)

Mounting:

Ceiling or Wall, Separate Mounting Brackets Provided

Wiring:

Plug with Attached Cable

Adjustment Angle:

Ceiling:

±30° Horizontal/60° Vertical

Wall: ±90° Horizontal/60° Vertical

Electrical (Receiver)
Voltage:

20 to 32 VDC

Maximum Ripple Voltage:

6.0 volts (Peak-to-peak)

Current (24 VDC):

Avg. Standby:

10mA Max.

Avg. Alarm:

28.4mA Max.

Avg. Trouble: 27.1mA Max.

Start-up Surge:

19mA Max.

Relay Contacts:

.5A at 30 VAC/DC

Reset Time:

.6 Seconds Max.

Start-up Time (after 5 min. reset): 1 Minute Maximum
Power Loss:

Retain Memory for 5 Minute Minimum

Electrical (Transmitter)
Voltage:

18.8 to 32 VDC

Maximum Ripple Voltage:

5.6 volts (Peak-to-Peak)

Avg. Current (24 VDC):

10mA Max.