System Sensor RTS151 User Manual

Rts151 remote test station, Installation and maintenance instructions

Advertising
background image

D440-01-00 1 I56-0469-014

NOTE: RTS151 replaces RTS451.
NOTICE: This manual shall be left with the owner/user of this equipment.
NOTE: A test coil is required only for use with D2/DNR/DH400/DH500 mod-
els. For D2 models order part #DCoil. For the DH400/500 models order part
is #Coil.

General InformatIon
System Sensor’s RTS151 is an automatic fire detector accessory designed to
test a remotely located detector. Consult detector installation instructions for
additional information.

The National Fire Protection Association has published codes, standards, and
recommended practices for the installation and use of the above product. It is
recommended that the installer be familiar with these requirements, with local
codes, and any special requirements of the local authority having jurisdiction.
rtS151 ContentS
1 RTS151 remote test station

1 screw pack (2 mounting screws)

1 M02-04 test magnet
WIrInG of rtS151
Consult the appropriate detector installation instructions for the applicable
wiring diagram. The RTS151 mounts to a single gang box (2

1

/

2

” minimum

depth), or directly to the wall or ceiling.
See Figure 8 for wiring diagram of RTS151 with Duct Smoke Detectors.

In Canadian applications, the RTS151 is intended to be located in the same
room as the smoke detector and within 60 feet of the unit.
operatIon
Test Function

Place and hold the painted side of the magnet to the test location RTS151.
Alarm Indication

With the magnet in place some time will elapse (40 sec. maximum) depend-
ing on the detector type, before the alarm indicating LED will light.
Reset Function

Gently insert a

1

/

8

˝ maximum diameter tool into the hole until it stops and

LED turns off. The RTS151 is capable of resetting only certain System Sensor
models of detectors. Refer to detector installation instructions for additional
information.

SpeCIfICatIonS
Dimensions:

4.8˝ H × 2.90˝ W × 1.4˝ D

Weight:

.16 lbs.

Power Requirements
Alarm LED:

2.8 – 32 VDC, 10 mA max.

Coil Current:

95 mA max.

Test Switch:

10 VA @ 32 VDC

Reset Switch:

10 VA @ 32 VDC

Alarm Response Time:

40 sec. max.

Temperature:

–10°C to 60°C (14°F to 140°F)

Humidity:

95% RH Non-condensing Max

Listing:

UL, FM, CE

fIGure 1. rtS151 remote teSt StatIon:

fIGure 2. WIrInG DIaGram for rtS151 to D4120 4-WIre DuCt
Smoke DeteCtor:

rtS151
remote test Station

InStallatIon anD maIntenanCe InStruCtIonS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

H0196-01

H0582-20

I56-0469-0

14

19
20

15

2

1
5

4

3

D4120

RTS151

(RED LED)

ALARM

FIELD

INSTALLED

JUMPER

11

2

AUX OUT +

AUX OUT –

ALARM
R TEST
R RESET

RTS451/RTS451KEY

RTS151/RTS151KEY

JUMPER

4

5

3

2

1

TEST COIL +

TEST COIL –

COMM +

OUT (CONV ONLY) +

COMM –

RA/RTS –

RA +

RTS +

H0633-00

fIGure 3. WIrInG DIaGram for rtS151 to Dnr 2-WIre DuCt
Smoke DeteCtor WItH remote teSt CapaBle HeaD: