System Sensor RTS151KEY(А) User Manual

Rts151key(a) remote test station, Installation and maintenance instructions

Advertising
background image

D440-03-00 1 I56-0758-015

RTS151KEY(A)
Remote Test Station

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

NOTE: RTS151KEY(A) replaces RTS451KEY.
NOTICE: This manual shall be left with the owner/user of this equipment.
NOTE: A test coil is required only for use with D2/DNR/DH400/DH500 mod-
els. For D2 models order part # DCOIL. For DH400/500 models order part #Coil.

GENERAL INfORMATION
The System Sensor RTS151KEY(A) is an automatic fire detector accessory de-
signed to test remotely located duct and beam detectors. For 4-wire detectors,
the RTS151KEY(A) features a multi-colored LED that alternates between steady
green and red. Green indicates power and that the detector board is in place.
Red indicates alarm. For 2-wire detectors, the LED will show red for alarm.
Consult the detector installation instructions for additional information.

The National Fire Protection Association has published codes, standards, and
recommended practices for the installation and use of this product. It is rec-
ommended that the installer be familiar with these requirements, with local
codes, and any special requirements of the local authority having jurisdiction.
RTS151 CONTENTS
1 RTS151KEY(A) remote test station

1 screw pack (2 mounting screws)

2 Keys
OpERATION
Test Function

Insert the key and turn clockwise to the “TEST” position.
Alarm Indication

With the key in the “TEST” position, some time will elapse (40 seconds maxi-
mum) depending on the detector type, before the alarm indicating LED will
turn red.
Reset Function

Turn the key counterclockwise to the “RESET” position and hold. The LED
should turn off. Then, turn the key back to the “NORMAL” position and re-
move. The RTS151KEY(A) is capable of resetting only certain models of detec-
tors. Refer to the detector installation instructions for additional information.
Wiring Instructions

Consult the appropriate detector installation instructions for the applicable
wiring diagram. The RTS151KEY(A) mounts to a single gang box (2

1

/

2

˝ mini-

mum depth), or directly to the wall or ceiling.

In Canadian applications, the RTS151KEY(A) is intended to be located in the
same room as the smoke detector and within 60 feet of the unit.

H0195-01

H0582-21

fIGURE 1. RTS151KEY(A)

fIGURE 2: WIRING DIAGRAM fOR RTS151KEY(A) TO D4120 4-WIRE
DUCT SMOKE DETECTOR:

fIGURE 3: WIRING DIAGRAM fOR RTS151KEY(A) TO DNR 2-WIRE
DUCT SMOKE DETECTOR WITH REMOTE TEST CApABLE HEAD:

SpECIfICATIONS
Dimensions:

4.6˝ H × 2.75˝ W × 1.8˝ D

Weight:

0.24 Lbs.

Power Requirements
Power LED (Green):

14 – 35 VDC, 12 mA maximum

Alarm LED (Red):

2.8 – 32 VDC, 12 mA maximum

Alarm Response Time:

40 seconds maximum

Temperature:

–10°C to 60°C (14°F to 140°F)

Humidity:

95% relative humidity, noncondensing Max

Listing:

UL, FM, CE

I56-0

758-0

15

19
20

15

2

6

1
5

4

3

D4120

RTS451KEY(A)

(GREEN LED)

POWER

(RED LED)

ALARM

FIELD

INSTALLED

JUMPER

11

2

AUX OUT +

AUX OUT –

ALARM
R TEST
R RESET

14

3

SUP, NO
SUP, C

* Sup. contacts cannot be used if they are wired to control panel.

*

RTS451/RTS451KEY

RTS151/RTS151KEY

JUMPER

4

5

3

2

1

TEST COIL +

TEST COIL –

COMM +

OUT (CONV ONLY) +

COMM –

RA/RTS –

RA +

RTS +

H0633-00