System Sensor 2151 - OLD STYLE User Manual

System Sensor Equipment

Advertising
background image

D100-04-00 1 I56-581-07R

2151 Low Profile
Photoelectronic Plug-in
Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Before Installing
Please thoroughly read the System Sensor manual A05-
1003, Applications Guide for System Smoke Detectors,
which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available from System Sensor.

NOTICE: This manual should be left with the owner/user
of this equipment.

IMPORTANT: The detector used with this base must be
tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.

General Description
The 2151 low-profile photoelectronic detector uses a state-
of-the-art optical sensing chamber. This detector is designed
to provide open area protection and to be used with com-
patible UL listed control panels only. The capability of plug-
ging this detector into a variety of special bases makes it
more versatile than equivalent direct-wired models.

Two LEDs on each detector provide local 360° visible
alarm indication. They flash every ten seconds indicating
that power is applied and the detector is working properly.
The LEDs latch on in alarm. Remote LED annunciator
capability is standard and may be implemented through
an optional accessory RA400Z. The alarm can be reset
only by a momentary power interruption. This detector
may be tested by activating the internal reed switch with
a magnet.

Base Selection And Wiring Guide
Refer to the installation instructions for the Plug-in
Detector Bases for base selection and wiring instructions.
System Sensor has a variety of detector bases available for

Specifications
Size
Height:

1.7 inches (43 mm)

Diameter:

4.0 inches (101 mm)

Weight:

3.6 oz. (102 g)

Operating Temperature Range:

0°C to 49°C (32°F to 120°F)

Operating Humidity Range:

10% to 93% Relative Humidity noncondensing

Latching Alarm:

Reset by momentary power interruption.

this smoke detector, including 2-wire applications with and
without relays and/or current limiting resistors, 4-wire and
120VAC applications.

All bases are provided with screw terminals for power,
ground, remote annunciator connections and relay contact
connections, if applicable. The electrical ratings for each
detector-base combination are also included in the base
installation instructions.

Installation
NOTE:
All wiring must conform to applicable local codes,

ordinances, and regulations.

NOTE: Verify that all detector bases are installed, that

the initiating-device circuits have been tested, and
that the wiring is correct. (Refer to detector base
manual for testing procedure.)

WARNING

Remove power from initiating-device circuits before install-
ing detectors.

1. Install detectors:
a. Place the detector into the detector base.
b. Turn the detector clockwise until the detector drops

into place.

c. Continue turning detector clockwise to lock it in

place.

2. Tamper Resistance: The detector bases can be made tam-

per resistant. When capability is enabled, detectors can-
not be removed from the base without the use of a tool.
See the detector base installation manual of the detector
base for details in using this capability.

3. After all detectors have been installed, apply power to

the control unit.

I56-
581
-07R

Advertising