System Sensor CO1224T and CO1224TR User Manual

Page 2

Advertising
background image

SS-500-000 2 I56-3111-006

inSTaLLaTiOn guideLineS
Ceiling: Detector should be at least 12 inches from any wall.

Wall: Detector should be at least as high as a light switch, and at least six
inches from the ceiling.

• Do not install in any environment that does not comply with the detec-

tor’s environmental specifications

• Install in accordance with NFPA 720–the Standard for the Installation of

Carbon Monoxide (CO) Detection and Warning Equipment

• As of 2009, NFPA 720 defines standards for both commercial and resi-

dential installations of CO detectors. If the installation can be interpreted
as a commercial application, consult the section of NFPA 720 that out-
lines commercial applications.

• For example, Chapter 5.5.5.3.1 states that carbon monoxide detectors

shall be installed in accordance with manufacturers published instruc-
tions in the following locations:

(1) On the ceiling in the same room as permanently installed fuel

burning appliances

(2) Centrally located on every habitable level and in every HVAC zone

of the building

• If the installation can be interpreted as residential, consult the section of

NFPA 720 that outlines residential applications.

• For example, chapter 9.4.1.1 states that carbon monoxide alarms or

detectors shall be installed as follows:

(1) Outside each separate dwelling unit sleeping area in the immedi-

ate vicinity of the bedrooms

(2) On every level of a dwelling unit, including basements

(3) Other locations where required by applicable laws, codes or standards

mOunTing
The CO1224T/CO1224TR can be ceiling-mounted or wall-mounted:

1. To a single gang box.
2. Direct mount to ceiling or to wall using drywall fasteners.
3. Mounted with optional replacement plate model CO-PLATE*.

inSTaLLaTiOn
Wiring inSTaLLaTiOn guideLineS
All wiring must be installed in compliance with the NFPA 70, National Electrical
Code, applicable state and local codes, and any special requirements of the local
Authority Having Jurisdiction (AHJ).

Proper wire gauges should be used. The conductors used to connect carbon
monoxide detectors to the alarm control panel and accessory devices should
be color-coded to reduce the likelihood of wiring errors. Improper connections
can prevent a system from responding properly in the event of a CO.

The screw terminals in the mounting base will accept 14-22 gauge wire. Wire
connections are made by stripping approximately

1

4

˝ of insulation from the

end of the feed wire, inserting it into the proper base terminal, and tightening
the screw to secure the wire in place. Do not put wires more than 2 gauge
apart under the same clamping plate.
WARNING: This product does not have a local audible trouble signal, and
may fail without supervision if trouble loop remains unconnected.
WARNING: Gas detectors on a zone that is bypassed may not signal a trouble
condition. Do not bypass zones used for gas detectors.
Wiring diagrams located on page 4, Figure 4.

WARNING

Remove power from alarm control unit or initiating device circuits before in-
stalling detectors.

1. Using a small, flat head screw driver, push in the small tab located on the
underside of the detector. Once the snap is loosened, lift the bottom end of
the cover up and unhinge the top to remove the cover.
2. Wire the detector base screw terminals per Figure 5.
3. Screw the base of the detector onto a single gang electrical box, or to the

surface of the wall or ceiling. Use the hardware included in the packaging.

4. If mounting with the System Sensor replacement plate model CO-PLATE*:

* Hold replacement plate over desired mounting area.

* Use hook feature to hold CO1224T onto the replacement plate.

* Mount detector and plate together using hardware provided with

the CO1224T.

5. Hinge the top portion of the cover onto the base; with the cover at a 45

degree angle, fit the hinges into the slots of the base.

6. Push the unhinged bottom portion of the cover down until it snaps into place.
7. After all detectors have been installed, apply power to the alarm control unit.
8. Test each detector as described in Testing.
9. Notify the proper authorities that the system is in operation.

CAUTION

Airborne dust particles can enter the detector. System Sensor recommends
the installation of detectors before beginning construction or any other dust
producing activity. Carbon monoxide detectors are not to be used with detec-
tor guards unless the combination has been evaluated and found suitable for
that purpose.

TeSTing
Detector must be tested after installation.
NOTE: Before testing, notify the proper authorities to avoid any nuisance
alarms.
Ensure proper wiring and power is applied. After power up, allow 80 seconds
for the detector to stabilize before testing.

Test the CO1224T/CO1224TR detector as follows:

1. A test button is located on the detector housing (See Figure 4).
2. Use the tip of your finger to press and hold the test button.
3. If the sounder beeps and the LED’s light up after 1-4 seconds, the detec-

tor is operational.

If a detector fails the above test method, its wiring should be checked. If the
detector still fails after rewiring, it should be replaced.

S0320-00

Figure 2. mOunTing OF deTeCTOr:

CO1224T

CO1224Tr

MOUNT DETECTOR TO

CENTER OF PLATE

S0296-01

S0319-00

Figure 3: mOunTing OF CO1224T deTeCTOr TO CO-pLaTe*

CO deTeCTOr repLaCemenT pLaTe

*NOTE: The CO-PLATE has not been evaluated or approved by a NRTL.

Advertising