1

I56-2964-002

APA151 Annunciator
with Piezo Alert

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

NOTICE: These models were only tested at the 16-33 Volt
DC limits. This does not include the 80% low-end or 110%
high-end voltage limits. This manual shall be left with the
owner/user of this equipment.
General Information
The National Fire Protection Association (NFPA) has pub-
lished codes, standards, and recommended practices for the
installation and use of this product. It is recommended that
the installer be familiar with these requirements, with local
codes, and any special requirements of the local authority
having jurisdiction. For further information, consult NFPA
72 and 90A requirements.
The System Sensor APA151 annunciator with piezo alert
is an audible signal appliance for fire alarm service. It is
intended for use in System Sensor 4-wire conventional duct
smoke detector applications without a system control panel
to comply with NFPA 90A.
The APA151 provides a red alarm LED, with an audible an-
nunciation of an alarm signal, and a green power LED.

Specifications
Dimensions:

4.6˝ L × 2.9˝ W × .45˝ D

Weight:

.17 lbs.

Electrical Requirements:

Voltage:

Regulated 24VDC

Operational Voltage:

16–33 VDC

Maximum Operating Current:

30mA

Connections:

#6 binding head screws, 12 AWG to 18 AWG wire

UL Reverberant Room:

81 dBA min. @ 10 ft.

Standard Operating Temperature:

0°C to 49°C (32°F to 120°F)

Humidity Range:

10% to 93% non-condensing