System Sensor B114LPBT User Manual

B114lpbt plug-in detector base, Installation and maintenance instructions

Advertising
background image

D150-07-00

1 I56-2169-001R

B114LPBT Plug-in Detector Base

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

SPECIfICATIONS
Base Diameter:

6.2 in (15.7 cm)

Base Height:

1.1 in (2.9cm)

Weight:

0.6 lb (260 g)

Mounting:

4˝ square box without plaster ring, minimum depth 1.5˝; 4˝ octagon box, minimum depth 1.5˝;

3

1

2

˝ octagon box, minimum depth 1.5˝

Operating Temperature Range:

0°C to 49°C (32°F to 120°F)

Operating Humidity Range:

10% to 93% Relative Humidity

Electrical Ratings (includes base and detector)
System Voltage:

24 VAC/DC, 60 Hz

Relay Contact Ratings Resistive Load: Form A — 2.0A @ 30VAC/DC; Form C — 2.0A @ 30VAC/DC, 1.0A @ 125VAC

(If used, the RA400 Remote Annunciator and RTC operates within the specified detector system voltage)

Standby Current:

25 mA typical @ 24V AC/DC; 35 mA maximum @ 35V AC/DC

Alarm Current:

75 mA typical @ 24V AC/DC; 94 mA maximum @ 35V AC/DC

Start-up Time (after 60 second reset): 36.0 Seconds maximum

BEfORE INSTALLINg
Please thoroughly read System Sensor’s manual I56-407, Guide for Proper Use
of System Smoke Detectors
. This manual provides detailed information on de-
tector spacing, placement, zoning, wiring, and special applications, and is
available at no charge from System Sensor.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be tested and maintained
regularly following NFPA 72 requirements. The detector used with this base
should be cleaned at least once a year.
gENERAL DESCRIPTION
The B114LPBT detector base is designed for use with System Sensor model
2151 photoelectronic and 1151 ionization detector heads. The capability of
plugging these detectors into a variety of special bases makes them more ver-
satile than equivalent direct-wired models. Refer to the System Sensor catalog
for other available plug-in bases. The B114LPBT base is intended for use in
4-wire systems with terminals provided for remote annunciator and relay con-
nections.
MOUNTINg
The detector base mounts directly to 3

1

/

2

- and 4-inch octagon boxes and 4-inch

square boxes. To mount the base, remove the decorative ring by rotating it in
either direction to unhook the snaps before separating the ring from the base.
Use the screws supplied with the junction box to attach the base to the box
through the appropriate mounting slots in the base.

Position the decorative ring around the base and rotate it in either direction
until the ring snaps into place (see Figure 2).

BASE TERMINALS

NO.

FUNCTION

NO.

FUNCTION

1

Remote Annunciator (+) 8

N.O.

Alarm Relay

2

Test Coil (+)

9

N.O.

Form A

3

Not Used

10

C.

Initiation

4

Remote Annunciator (–) 11

C.

Contacts

5

RTC (–)

12

N.O.

Alarm Relay

6

C.

Supervisory Relay

13

N.C.

Form C

7

N.O. Form A Contacts

14

C.

Auxiliary Contacts

INSTALLATION gUIDELINES
All wiring must be installed in compliance with the National Electrical Code,
all applicable local codes, and any special requirements of the authority hav-
ing jurisdiction, using the proper wire size. The conductors used to connect
smoke detectors to control panels and accessory devices should be color-coded
to reduce the likelihood of wiring errors. Improper connections can prevent a
system from responding properly in the event of a fire.

For signal wiring (the wiring between interconnected detectors), it is recom-
mended that the wire be no smaller than 16 gauge (1.5 square mm), and that

two- or three-conductor wire be no smaller than 18 gauge (1.0 square mm).
For best performance, alarm loop conductors should be installed in separate
grounded conduit or shielded cable to protect the alarm loop from extraneous
electrical interference.

Smoke detectors and alarm systems control panels have specifications for al-
lowable loop resistance. Consult the control panel manufacturer’s specifica-
tions for the total loop resistance allowed for the particular model control
panel being used before wiring the detector loops.
fIgURE 1. BASE TERMINALS:

BASE

TERMINALS

SHORTING

SPRING

STRIP GAUGE

1

2

3

5

4

TAMPER

RESISTANT TAB

6

7

8

9

10

11

12

13 14

24VDC/24VAC

TERMINALS

C1025-00

fIgURE 2. MOUNTINg BASE TO BOx:

SNAP ON

DECORATIVE

RING

SCREWS

(NOT SUPPLIED)

DETECTOR

BASE

BOX

(NOT SUPPLIED)

SHORTING

SPRING

C0503-00

I56-2

169-00

1R

For use with the following smoke detectors: US - 1151, 2151, 2151T;
CANADA - 1151A, 2151A, 2151TA; EUROPE - 1151E, 2151E