Alarm + aux out, D2 duct detector – System Sensor D2 User Manual

Page 6

Advertising
background image

ALARM +

AUX OUT –

(+)

(–)

RED

RA400Z/RA100Z

(OPTIONAL)

REMOTE (LED)

ANNUNCIATOR

D2

DUCT DETECTOR

fIgURE 10. wIRINg DIAgRAM fOR RTS451/RTS151/RTS451kEy/RTS151kEy REMOTE TEST STATION TO
2-wIRE D2 DUCT DETECTOR:

24 VAC (+10%, –15%)

FULL WAVE RECTIFIED,

UNFILTERED POWER

MAY BE USED

RTS451/RTS451KEY

(OPTIONAL) REMOTE

TEST STATION

MAGNET

TEST

SWITCH

ALARM

LED (RED)

4

5
2

1

(+)

(–)

+ RA

+ RTS

– RA

+ TEST COIL

– TEST COIL

+ IN

+ OUT

(–)

(+)

D2

24 VDC

AUX POWER

SUPPLIED

BY USER

(100mA

SUPPLY)

RTS451/RTS451KEY

(OPTIONAL) REMOTE

TEST STATION

24 VAC (+10%, –15%)

FULL WAVE RECTIFIED,

UNFILTERED POWER

MAY BE USED

MAGNET

TEST

SWITCH

ALARM

LED (RED)

4

5

2

1

(+)

(–)

+ RA

+ RTS

– RA

+ TEST COIL

– TEST COIL

+ IN

+ OUT

24 VDC

AUX POWER

SUPPLIED

BY USER

(100mA

SUPPLY)

D2

NOTE: THE USE OF EITHER THE RTS451 OR RTS451KEY REQUIRES THE INSTALLATION OF AN ACCESSORY COIL, DCOIL, SOLD

SEPARATELY. SEE FIGURE 9 ABOVE FOR REFERENCE.

METHOD #1 - AUX POWER LOCATED

AT DUCT DETECTOR

METHOD #2 - AUX POWER LOCATED

AT TEST STATION

H0612-02

SS-300-014

6 I56-3050-004R

©2012 System Sensor

ThREE-yEAR LIMITED wARRANTy

System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for the enclosed product.
No agent, representative, dealer, or employee of the Company has the authority to in-
crease or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the replacement of any part of the product which
is found to be defective in materials or workmanship under normal use and service
during the three year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns Department, RA

#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing
the malfunction and suspected cause of failure. The Company shall not be obligated to
replace units which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.

Please refer to insert for the Limitations of Fire Alarm Systems

[13] OPTIONAL ACCESSORIES
The D2 duct smoke detector can be used with the RA400Z/RA100Z, RTS451/
RTS151, or RTS451KEY/RTS151KEY remote test station.

fIgURE 9. D2 wITh OPTIONAL TEST COIL:

TEST COIL TERMINALS

TEST COIL

TEST COIL SCREW

H0561-00

H0611-05

fIgURE 8. wIRINg DIAgRAMS fOR OPTIONAL ACCESSORIES:

[13.1] RTS451/RTS151/RTS451kEy/RTS151kEy REMOTE TEST
STATION
The RTS451/RTS151/RTS451KEY/RTS151KEY Remote Test Station facilitates
test of the alarm capability of the duct smoke detector as indicated in the
RTS451/RTS151/RTS451KEY/RTS151KEY manual. The D2 duct smoke detector
must be reset by the system control panel. If a system control panel is used,
the panel itself may also require testing.

To install the RTS451/RTS151/RTS451KEY/RTS151KEY, connect the device as
shown in Figure 10 on page 6; wire runs must be limited to 25 ohms or less
per interconnecting wire.

NOTE: The use of a remote test station requires the installation of an acces-
sory coil, part number DCOIL, sold separately. See Figure for reference.
1) Install DCOIL in housing pocket insuring that arrow is pointing toward detector
2) Install DCOIL mounting screw
3) Connect each DCOIL lead to a Test Coil Terminal

Advertising