System Sensor D4120, D4P120, and D4S User Manual

Page 5

Advertising
background image

SS-300-000

5 I56-2967-006R

FIGURE 7. SYSTEM WIRING DIAGRAM FOR 4-WIRE DUCT SMOKE DETECTORS:

CAUTION

Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.

24VAC/DC

9

10

AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC. (NOTE 2)

16

6

17

8

18

7

N.O.

C.

N.C.

N.O.

C.

N.C.

16

6

17

8

18

7

N.O.

C.

N.C.

N.O.

C.

N.C.

SUPERVISORY CONTACTS

(NOTE 3)

24V

9

10

AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC. (NOTE 2)

SUPERVISORY CONTACTS

(NOTE 3)

SUP N.O.

SUP C

SUP C

SUP N.O.

4

5

ALARM

INITIATION

CONTACTS

(NOTE 4)

4

5

ALARM

INITIATION

CONTACTS

(NOTE 4)

ALARM

INITIATION

LOOP

UL/FM LISTED

4-WIRE

CONTROL PANEL

+

120

VAC

120

VAC

OR

OR

AUX A

AUX B

AUX A

AUX B

ALARM N.O.

ALARM N.O.

ALARM C

ALARM C

3

3

14

14

FIRST DETECTOR IN THE LOOP

POWER INPUTS (NOTE 1)

POWER INPUTS (NOTE 1)

LAST DETECTOR IN THE LOOP

EOL RESISTOR

SPECIFIED BY

PANEL

MANUFACTURER

NOTE 1: 24V Power Inputs accept a non-polarized 24VDC or 24VAC 50-60Hz.
120VAC Power Inputs accept only 120VAC 50-60Hz. Connect power source to
appropriate terminals of each detector. See specifications for additional power
supply information.
NOTE 2: Auxiliary contacts shown in standby position. Contacts switch dur-
ing alarm as indicated by arrows. Auxiliary contacts are not to be used for
connection to the control panel. See specifications for contact ratings.
NOTE 3: Supervisory contacts shown in standby position. Open contacts indi-
cate a trouble condition to the panel. See specifications for contact ratings.
NOTE 4: Alarm Initiation contacts shown in standby position. Closed contacts
indicate an alarm condition to the panel. See specifications for contact ratings.

H0558-07

Designation

Default

Selection

Features

TRBL SHUTDN

OFF

OFF

Aux relay does not switch states with a Trouble condition

ON

Aux relay switches states with a Trouble condition

SENSORS

1

1

Only one sensor is connected the Power Board

2

Two sensors are connected to the Power Board

MIN TMPR

DELAY

7

7

Provides a Trouble condition ( terminals 3 and 14 open) when Sensor Housing cover has

been removed or has been secured improperly for more than 7 minutes

0

Provides an instantaneous Trouble condition(terminals 3 and 14 open) upon cover removal

TABLE 2. DIP SWITCH SETTINGS:

[10] DETECTOR STATUS INDICATION
Detector Staus is indicated by the LED sensor, and the correcsponding LED on
the power board. The power board has two separate LED’s to indicate the sta-
tus of each sensor connected to it. Refer to Table 3 on page 8 for more details.
[11] INTERCONNECTION (MULTIPLE FAN SHUT DOWN)
When using the interconnect feature, an alarm from an initiating device will
switch the Aux Relays on the other devices interconnected.