System Sensor DH100ACDCI User Manual

Page 7

Advertising
background image

ALARM SIGNAL (+)

AUX POWER (–)

15

20

(+)

(–)

DUCT DETECTOR

DH100ACDCI

PA400 (OPTIONAL)

AUDIBLE ALERT

ALARM SIGNAL (+)

AUX POWER (–)

15

20

(+)

(–)

DUCT DETECTOR

DH100ACDCI

RA400Z (OPTIONAL)

REMOTE (LED)

ANNUNCIATOR

RED

ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE
APA451
PA400
RA400Z
RTS451/RTS451KEY
SSK451

STANDBY
12.5mA Max.
0mA
0mA
12mA*
5mA Max.

ALARM
30mA Max.
15mA Max.
10mA Max.
7.5mA Max.
30mA Max.

*NOTE: When a unit is powered at the 120VAC or 220/240VAC input, any

combination of accessories may be used such that the given accessory loads are:

60 mA or less in the standby state; 110 mA or less in the alarm state.

TROUBLE
n/a
n/a
n/a
n/a
9mA Max.

D100-68-00

7

I56-1684-007R

Figure 11. Wiring diagrams for optional accessories:

H0402-01

15

ALARM SIGNAL

3
14
2

RESET

11

TEST

20

AUX. POWER (-)

19

AUX. POWER (+)

SSK451

FIELD INSTALLED

JUMPER FOR

TEMPORAL PATTERN

SUPERVISORY

CONTACT

NO

FIELD INSTALLED

JUMPER

DH100ACDCI

COMMON 3

TEMPORAL SELECT 2

ALARM SIGNAL 1

SUPERVISORY SIGNAL 4

RESET 7

TEST 8

POWER (-) 6

POWER (+) 5

Figure 12. Wiring diagram for DH100ACDCI to SSK451:

H0403-00

Figure 13. Testing detector alarm:

H0404-00