System Sensor DH400ACDCIHT User Manual

Page 11

Advertising
background image

D400-64-00 11 I56-991-08R

F36-05-00 Replacement Air Filter (two per package)
M02-04-01 Replacement Test Magnet
P48-21-00 Replacement End Plug for inlet sampling tube
RS14 Replacement Screen, Ion
A2650-01 Replacement Installation Kit (mounting hardware)
DH400 OE-1 Enclosure for outdoor applications
Sampling (Inlet) Tubes
TUBE OUTSIDE DUCT WIDTH
ST-1.5 1 to 2 feet

(0.3 to 0.6 m)

ST-3 2 to 4 feet

(0.6 to 1.2 m)

ST-5 4 to 8 feet

(1.2 to 2.4 m)

ST-10 8 to 12 feet (2.4 to 3.7 m)
Exhaust Tube Extension
A2440-00 5.75 in. (14.6 cm.) additional

Electrical Specifications
Power supply voltage: 20-29 VDC 24 VAC 50-60-Hz 120 VAC 50-60 Hz 220/240 VAC 50-60 Hz
Input capacitance: 270 µF max. 270 µF max. N/A N/A
Reset voltage: 3.0 VDC or less 2.0 VAC or less 10 VAC or less 20 VAC or less
Reset time (by power down): 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. 0.6 sec. max.
Power up time: 34 sec.max. 34 sec. max. 34 sec. max. 34 sec. max.
Alarm response time: 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. 2 to 17 sec.

Electrical Ratings

[8] DH400 OE-1 Optional Accessory
General Description
The DH400 OE-1 all-weather enclosure is specifically
designed to house and protect the System Sensor model
DH400ACDCIHT high temperature duct detector from the
elements. This enclosure provides protection in outdoor
installations against rain, sleet, and snow or in indoor
installations against dripping water.

NOTE: The DH400 OE-1 is designed solely for the use

with System Sensor model DH400ACDCIHT high
temperature duct smoke detector.

Preparation
Locate the two adhesive backed gaskets packaged with the
enclosure.

NOTE: In order to provide effective sealing, these gaskets

must be placed on the outside of the enclosure
around the two large openings.

Remove the protective paper. Place the gaskets around the
large openings, aligning the screw holes of the gaskets with
the screw holes of the enclosure. Press firmly to insure
complete adhesion.

Power Supply Voltage

20-29 VDC

24VAC 50-60 Hz

120 VAC 50-60 Hz

220/240 VAC 50-60 Hz

CURRENT REQUIREMENTS (USING NO ACCESSORIES)*

Max. standby current

25 mA

35 mA AC avg.

20mA AC avg.

20mA AC avg.

Max. alarm current

95 mA

55 mA AC avg.

55 mA AC avg.

30 mA AC avg.

*NOTE: Accessories require extra current. Refer to accessory device manual.

CONTACT RATINGS

Alarm initiation contacts (SPST) 2.0A @ 30 VAC/DC (0.6 power factor)
Alarm auxiliary contacts (DPDT) 10A @ 30 VDC Resistive
10A @ 250 VAC
NOTE: Alarm auxiliary contacts must switch 500 mA minimum at 24 VDC. Alarm auxiliary contacts shall not be
connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose.
Trouble contacts (SPST) 0.3A @ 32 VDC (resistive)