18. Put detector into alarm using appropriate method

described in STEP 7. PERFORM DETECTOR CHECK
(page 7 of this manual).

19.

Notify the proper authorities that testing has been
completed and the smoke detector system is again
operational.

20.

Other checks that should be made during mainte-
nance procedures:
–Holes or cracks in duct work near vicinity of detec-
tor
–Air leaks where detector housing or sampling tubes
are attached to duct
–Dust accumulations in or on sampling tubes
–Wiring terminal screw tightness

Accessories

Part No.

Remote LED

RA400ZA

Remote Test Station

RTS451/RTS451KEY

Piezo Alert Sounder

PA400

Replacement Filters

F36-05-00

Magnet

M02-04-00

End Plug For Sampling Tube

P48-21-00

Installation Kit (Parts bag)

A2650-01

Ionization Replacement Screen

RS14

Sensitivity Test Kit

MOD400

Ionization Cover Removal Tool

CRT400

Programming Specifications/Requirements for

Intelligent System Control Panels

The 1551 and 2551 models can be used with the DH500 if
the following constraints are observed.

There is a limit to the number of devices per zone that can
have their LEDs latched ON. The actual number of devices
is determined by the control panel and its ability to supply
LED current. Refer to the equipment manual supplied by
the control panel manufacturer for details.