Ra + ra, Remote alarm led option 1 per unit – System Sensor DNRECL User Manual

Page 5

Advertising
background image

SS-300-019

5 I56-3496-004R

*Aerosol smoke can be purchased from Home Safeguard Industries at home-
safeguard.com, model 25S Smoke Detector Tester, and Chekkit Smoke De-
tector Tester model CHEK02 and CHEK06 available from SDi. When used
properly, the canned smoke agent will cause the smoke detector to go into
alarm. Refer to the manufacturer’s published instructions for proper use of the
canned smoke agent.

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by
manufacturer. Misuse or overuse to these products may have long term ad-
verse effects on the smoke detector. Consult the canned smoke agent manufac-
turer’s published instructions for any further warnings or caution statements.

[9]DETECTOR CLEANING PROCEDURES
Notify the proper authorities that the smoke detector system is undergoing
maintenance, and that the system will temporarily be out of service. Disable
the zone or system undergoing maintenance to prevent unwanted alarms and
possible dispatch of the fire department.
[9.1]DETECTOR SENSOR
1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover by pressing firmly on each of the four removal

tabs that hold the cover in place.

3. Vacuum the screen carefully without removing it. If further cleaning is

required continue with Step 4, otherwise skip to Step 7.

4. Remove the chamber cover/screen assembly by pulling it straight out.
5. Use a vacuum cleaner or compressed air to remove dust and debris from

the sensing chamber.

6. Reinstall the chamber cover/screen assembly by sliding the edge over the

sensing chamber. Turn until it is firmly in place.

7. Replace the cover using the LEDs to align the cover and then gently

pushing it until it locks into place.

8. Reinstall the detector.
[9.2]REINSTALLATION
1. Reinstall the detector in its housing.
2. Restore system power.
3. Perform Detector Check.
4. Notify the proper authorities testing has been completed and the smoke

detector system is back in operation.

[10]SENSOR REPLACEMENT
1. Remove the sensor head by rotating counterclockwise.
2. Pull gently to remove it.
3. To replace the sensor head, align the mounting features and rotate clock-

wise into place.

[11] OPTIONAL ACCESSORIES
Optional accessories include RA400Z/RA100Z, RTS451/RTS151 and RTS-
451KEY/RTS151KEY
FIGURE 8. WIRING DIAGRAM FOR DNRECL TO RA400Z/RA100Z:

(+)

(-)

RA400Z/RA100Z

– RA

+ RA

REMOTE ALARM LED

OPTION 1 PER UNIT

H0570-03

Note: Tab on the RA400Z should be broken for use with the intelligent duct
smoke detector.

RTS451/RTS451KEY

FIELD WIRED

WIRE CONNECTION

REMOTE TEST STATION

LED OPTION

1 PER UNIT

8mA CURRENT DRAW

4

5

3

2

1

TEST COIL +

TEST COIL –

COMM +

OUT (CONV ONLY) +

COMM –

RA/RTS –

RA +

RTS +

FIGURE 9: WIRING DIAGRAM FROM DNRECL TO RTS451/RTS151/
RTS451KEY/RTS151KEY

HO571-11