SS-400-006

5 I56-3535-002R

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by
manufacturer . Misuse or overuse to these products may have long term ad-
verse effects on the smoke detector . Consult the canned smoke agent manufac-
turer’s published instructions for any further warnings or caution statements .

[9]DETECTOR CLEanInG PROCEDuRES
Notify the proper authorities that the smoke detector system is undergoing
maintenance, and that the system will temporarily be out of service . Disable
the zone or system undergoing maintenance to prevent unwanted alarms and
possible dispatch of the fire department .
[9.1]DETECTOR SEnSOR
1 . Remove the sensor to be cleaned from the system .
2 . Remove the sensor cover by pressing firmly on each of the four removal

tabs that hold the cover in place .

3 . Vacuum the screen carefully without removing it . If further cleaning is

required continue with Step 4, otherwise skip to Step 7 .

4 . Remove the chamber cover/screen assembly by pulling it straight out .
5 . Use a vacuum cleaner or compressed air to remove dust and debris from

the sensing chamber .

6 . Reinstall the chamber cover/screen assembly by sliding the edge over the

sensing chamber . Turn until it is firmly in place .

7 . Replace the cover using the LEDs to align the cover and then gently

pushing it until it locks into place .

8 . Reinstall the detector .

[9.2]REInSTaLLaTIOn
1 . Reinstall the detector in its housing .
2 . Restore system power .
3 . Perform Detector Check .
4 . Notify the proper authorities testing has been completed and the smoke

detector system is back in operation .

[10]SEnSOR REPLaCEmEnT
1 . Remove the sensor head by rotating counterclockwise .
2 . Pull gently to remove it .
3 . To replace the sensor head, align the mounting features and rotate clock-

wise into place .

[11] OPTIOnaL aCCESSORIES
Optional accessories include RA400Z/RA100Z, RTS451/RTS151 and

RTS451KEY/RTS151KEY .
NOTE: Ensure blue wire always remains connected to RA+ on the field
connector side of the terminal block.

(+)

(-)

RA400Z/RA100Z

– RA

+ RA

REMOTE ALARM LED

OPTION 1 PER UNIT

fIGuRE 9. wIRInG DIaGRam fOR DnRHS TO Ra400Z/Ra100Z:

H0570-03

Note: If using a RA400Z, the tab should be broken for use with the intelli-
gent duct smoke detector. If using RA100Z, ensure that jumper is removed

The RTS451/RTS151/RTS451KEY/RTS151KEY Remote Test Station facilitates
test of the alarm capability of the duct smoke detector . These accessories pro-
vide the stimulus to initiate an alarm condition at the detector . The DNRHS
duct smoke detector must be reset by the system control panel .

TEST COIL TERMINALS

DCOIL

TEST COIL SCREW

H0561-01

fIGuRE 10. DnRHS wITH TEST COIL

SENSOR COVER

COVER REMOVAL TABS

SCREEN ASSEMBLY

SENSING

CHAMBER

C0170-00

fIGuRE 11. LaSER HEaD EXPLODED VIEw: