Figure 2. Ring Replacement:

Figure 3. RTC100 Wiring Diagram:

A. Ring Replacement
1. Remove the decorative ring from the B114LP/

B114LPBT base by rotating it in either direction to
release the hooks. Separate the ring from the base.

2. Position the Test Coil Replacement Ring Assembly on

the base, as shown in Figure 2. Be sure to position the
test coil directly over the 4-Position Terminal Block.
Otherwise, the coil may not activate the switch during
a test.

3. Route the the Test Coil Replacement Ring Assembly

wires through the slot in the base as indicated in
Figure 2.

4. Rotate the ring in either direction until it snaps in

place. Dress all wiring, as needed.

B. Wiring
1. Route four wires from the B114LP/B114LPBT to the

test station mounting location. Be sure to comply
with all applicable electrical codes when installing
this wiring. This includes selecting the proper wire
size and routing through conduit, if necessary.

2. Connect the wiring to the B114LP/B114LPBT Base and

RTS451 Test Station, as shown in Figure 3.

C. Test Station Mounting
Attach the test station to a standard 2″ × 4″ electrical

box, using the screws supplied with the box.

Operation
Test
Position the painted side of the test magnet on the RTS451
Test Station on either the left or right side of the LED as
shown in Figure 1. The LED should light within 40 seconds,
indicating that the detector being is latched in alarm.

Reset
Reset the detector by inserting a narrow bladed pocket
screwdriver, or other similar tool, into the RESET hole
on the front of the test station. Gently press until the LED
turns off.

H0199-01

1

B114LP/B114LPBT

RTS451

2

3

4

5

1

2

3

4

5

REMOTE

ANNUNCIATOR (+)

TEST COIL (+)

RTC (–)

RESET

ALARM

TEST

COIL

System Sensor warrants its enclosed smoke detector to be free from de-
fects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part
of the smoke detector which is found to be defective in materials or work-
manship under normal use and service during the three year period com-
mencing with the date of manufacture. After phoning System Sensor’s toll
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Returns Depart-

Three-Year Limited Warranty

ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifica-
tions, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or con-
sequential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.

TEST

COIL

K1

RELAY

4-POSITION

TERMINAL

BLOCK

3-POSITION

TERMINAL

BLOCK

H0234-01

Advertising